Diagnosis and repairs
Refer to the tables below to resolve your problems.
The freezer heads do not ice up
Diagnosis:
The freezer is not connected.
The freezing time is not long enough.
Contact between freezer head, refrigerating
clamp and pipe does not offer adequate cold
exchange.
The temperature of the water in the pipes is
too high.
The pumps have not stopped, water still
circulates.
The flexibles or the equipment is defective.
Ice does not form on the tube
Diagnosis:
The freezing time is not long enough.
The temperature of the water in the pipes is
too high.
Contact between freezer head, refrigerating
clamp and pipe does not offer adequate cold
exchange.
The pumps have not stopped, water still
circulates.
The pipe does not freeze even though ice forms
Diagnosis:
The liquid to be frozen contains antifreeze.
The freezing times are longer than those indicated in the table.
Diagnosis:
The temperature of the water in the pipes is
too high.
The pumps have not stopped, water still
circulates.
Sun rays are affecting the point to be frozen.
The tube to be frozen is painted or rusted.
The unit fan blows on the part to be frozen.
The freezer head no longer fits in the refrigerating clamp
Diagnosis:
The refrigerating clamps has sustained an
impact and is bent out of shape.
Solution:
Connect the Siberia freezer.
Continue the freezing for some time.
Spread heat-conducting paste between each
element.
Continue the freezing.
Stop the pumps.
Return the unit to Virax After-Sales Service
Solution:
Continue the freezing for some time.
Continue the freezing.
Spread heat-conducting paste between each
element.
Stop the pumps.
Solution:
Remove or make remove the antifreeze from
the network.
Solution:
Continue the freezing.
Stop the pumps.
Prevent the rays from affecting the point to be
frozen.
Scour the tube clean.
Move the unit.
Solution:
Return the device to the Virax After-Sales
Service
EN