Chimney Pot; Connection To The Chimney; Connecting A Fireplace Or Open Hearth To The Flue - Nordica TERMOSUPREMA Compact-DSA Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

The following materials are FORBIDDEN and compromise the good operation of the appliance: asbestos cement, galvanised steel, rough and
porous internal surfaces.
Picture 1
For a correct installation please respect the sections/lengths of the flue shown in the technical data table. By installations
with different dimensions the flue must be suitably sized in accordance with EN13384-1.
The draught created by your flue must be sufficient but not excessive.
a section of the flue which is too large can present a volume which is too large to heat and therefore cause operating difficulties for the
appliance; to avoid this, it is necessary to intubate the appliance for its entire height. a section which is too small causes a reduction in draught.
ATTENTION: as far as concern the realisation of the flue connection and flammable materials please follow the requirements
provided by Uni 10683 standard. The flue must be at a suitably distance from flammable or combustible material using
suitable insulation or an air space.
it is FORBIDDEN to pass system piping or air ducts inside the flue. it is also forbidden to create moveable or fixed openings on
the flue itself, for the connection of further different appliances (see chapter ConneCTinG a fiRepLaCe oR open HeaRTH To THe
fLUe).

CHIMNEY POT

The flue draught depends on the suitability of the chimney pot.
it is therefore essential that, if built in a handcrafted way, the exit section is more than twice the internal section of the flue
as it must always go past the ridge of the roof, the chimney pot must ensure exhaust even in the presence of wind
The chimney pot must meet the following requirements:
Have an internal section equivalent to that of the chimney.
Have a useful exit section of double the internal section of the flue.
Be built so as to prevent rain, snow or any foreign body entering the flue.
Be easy to inspect, for any maintenance and cleaning operations.

CONNECTION TO THE CHIMNEY

products with automatic door closing (type 1) must operate, for safety reasons, with the furnace door closed (except during the fuel loading
or ash removal phases).
products with non-automatic door closing (type 2) must be connected to their own flue.
operation with doors open is only allowed when supervised.
The connection pipe to the flue must be as short as possible, straight horizontal and positioned slightly in ascent, and watertight.
Connection must be carried out with stable and robust pipes,comply with all current standards and Regulations and to those envisioned by
the law, and be hermetically secured to the flue. The internal diameter of the connection pipe must correspond to the external diameter of
the appliance flue gas exhaust stub pipe (din 1298).
ATTENTION: as far as concern the realisation of the flue connection and flammable materials please follow the requirements
provided by Uni 10683 standard. The flue must be properly spaced from any flammable materials or fuels through a proper
insulation or an air cavity. Minimum distance safety 25 cm.
IMPORTANT: the unused flue gas exhaust hole must be covered with its respective cap (see chapter: diMensions).
The chimney pressure (dRaUGHT) must be at least 12 pa pascal (=1.2 mm of water column). The measurement must always be carried out
when the appliance is hot (nominal calorific power). When the pressure exceeds 17 pascal, it is necessary to reduce it through the installation
of an additional draught regulator (false air valve) on the exhaust pipe or in the chimney, according to the regulations in force.
for correct appliance operation, it is essential that sufficient air for combustion is introduced into the place of installation (see
paragraph VenTiLaTion and aeRaTion of THe insTaLLaTion pReMises).

CONNECTINg A FIREPLACE OR OPEN HEARTH TO THE FLUE

The flue gas channel is the stretch of piping which connects the product to the flue. in the connection, these simple but extremely important
principles must be respected:
under no circumstances use a flue gas channel with a diameter less than that of the exhaust clamp with which the product is equipped;
each metre of the horizontal stretch of the flue gas channel causes a slight loss of head which must be compensated if necessary by
elevating the flue;
the horizontal stretch must never exceed 2 metres (Uni 10683);
each bend of the flue gas channel slightly reduces the flue draught which must be compensated if necessary by elevating it suitably;
The Uni 10683 – iTaLY regulation requires that under no circumstances must there be more than 2 bends or variations in direction
including the intake into the flue.
if the user wishes to use the flue as a fireplace or open hearth, it is necessary to seal the hood below the entrance point of the flue gas channel
pos. A
Picture
5.
if the flue is then too big (e.g. 30x40cm or 40x50cm), it is necessary to intubate it with a stainless steel tube with a diameter of at least 200mm,
pos. B, taking care to close the remaining spaces between the pipe and the flue immediately under the chimney pot pos. C.
30
shows some example solutions.
ENgLIsH
(Picture
2) .
(Picture
3).

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Italy termo-dsa

Table des Matières