Télécharger Imprimer la page

TDK-Lambda FPS-TB Directives D'installation page 24

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 5
A/D so that on every read data from each channel is read. Note that on each read. a conversion is started for a particular
channel and the result which will be displayed and will be of the previous read. (i.e. the previous channel).
Thus second read cycle gives result of the actual channel.
Note: the first result from a sequence of reads should not be considered.
FPS1000-12/S
0~15V
0.0586 V/Bit
0~80A
0.312 A/Bit
0~100ϒ C
0.391ϒC/Bit
FPS1000-32/S
Model: FPS1000-48 /S
Measurements and calculation examples
Output voltage readback
1. Output voltage (at the output terminals): 48.0V
2. Voltage before the "Oring" diode: 48.0V+0.5V=48.5V
3. Hex readback: CE (1100 1110).
4. Convert the hex readback to decimal: 206
5. Calculate measured Vout: Vout=206*0.2344=48.286V
FPS1000-24/S
FPS1000-48/S

Publicité

loading