_______________________________________________________________________________________________________________________________
Please note: You may not begin to use the wood burning stove until it has been inspected and approved by your
local chimney sweep.
2.1 Position of the stove/distance requirements
The new wood burning stove must be installed in a suitable and physically possible position. You need to be sure
that the position complies with local regulations. Distance requirements will only apply if the wood burning stove is
to be placed close to flammable materials. See below.
If the stove is positioned against a brick wall or other non-flammable material, there is no minimum distance
requirement. To facilitate cleaning and for the best use of the convection air, we recommend that you leave a
distance of approximately 5–10 cm to the wall. The Aduro 15/15.1 is built as a convection stove. This means that
air from the room circulates between the inner stove and the outer covering. As a result, the heated air is
distributed evenly throughout the room.
Distance to flammable material
Behind the stove
Behind stove with
To the sides of the
To furniture
insulated flue pipe
stove
20 cm
12 cm
34/11 cm
120 cm
Please note: that the Aduro 15/15.1 must be installed on a floor with the adequate load-bearing capacity. If the
existing construction does not meet this requirement, appropriate adaptation measures must be taken (e.g. a load-
distributing plate).
If the wood burning stove is to be placed close to flammable material, such as a wooden floor or carpet, it must be
placed on a non-flammable base. The floor plate should extend for at least 30 cm in front of the wood burning
stove, and 15 cm on each side – measured from the combustion chamber opening.
25