Ecoflam BLU 1700.1 PR Mode D'emploi page 13

Masquer les pouces Voir aussi pour BLU 1700.1 PR:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 26
Start up
- Air pressure switch adjustment - Setting gas pressostat
Air pressure switch calibration
The air pressure switch is provided for
monitoring the pressure of the
combustion air fan. Unscrew screws A and
B and remove cover C.
• Adjust the combustion with air pressure
switch (APS) set at minimum.
• Start to obstruct the air inlet with a paper
paying attention to O2 and CO values red
on the analyzer.
• Progressively increase air inlet
obstruction till the CO valve is slightly
more than 1000 ppm. Stop obstruction in
this position.
• Increase APS setting up to burner lock
out.
• Now the APS is set to avoid CO
production during the combustion.
• Remove air obstruction and fit again APS
cover C.
Min gas pressure switch
The gas pressure switch has the function
to check that the gas pressure before the
gas valve does have the minimum
pressure to make the burner running
correctly.
Unscrew off and remove cover M.
- Set knob N to a value equal to 60% of
gas nominal feed pressure (i.e. for natural
gas nom. pressure = 20 mbar, set knob to
a value of 12 mbar; for LPG nom. pressure
of G30/G31- 30/37 mbar, set knob to a
value of 18 mbar). Screw up cover M.
420010829900
C
A
B
M
I
L
www.ecoflam-burners.com
EN
D
N
13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Blu 2000.1 prBlu 1700.1 pr tcBlu 1700.1 pr tlBlu 2000.1 pr tcBlu 2000.1 pr tl3140401 ... Afficher tout

Table des Matières