QM8 HANDBOOK
Number
Module
Note
of slots
SC
-
2
SC
-
2
SC
-
2
SC
-
2
SC
-
2
ZC
-
2
ZC
-
2
ZC
-
2
ZD
-
3
ZD
-
3
ZD
-
3
ZD
-
3
ZF
6
4
ZF
-
4
ZF
9
4
ZF
-
4
ZH
10
6
ZT
-
3
ZV
-
4
Note 1: CH1 limited to 80W when CH2 at 120W. Maximum of 200W across module.
Note 2: CH2 Limited to 80W when CH1 at 120W. Maximum of 200W across module.
Note 3: CH2 has a maximum of 100W. Maximum of 200W across the module.
Note 4: CH1 (24V) has a reduced adjustment range when CH2 is 24V. Reduced adjustment range is 21.6V
to 28.8V.
Note 5: CH1 limited to 100W when CH2 at 100W. Maximum of 200W across module. Achievable if the
ambient temperature is reduced to 40°C.
Note 6: Please see Further De-ratings Table below
Note 7: KQM5001V-x model only
Note 8: 12/12DM Module limited to 180W in slot 2 or 45°C ambient.
Note 9: 67A for 10 seconds
Note 10: 1500W at high-line
Note 11:N/A
Output
Vout
Channe
nom (V)
l
CH1
17
17 to 18.7
CH1
24
24 to 26.4
CH1
30
30 to 33
CH1
36
36 to 39.6
CH1
48
48 to 52.8
CH1
15
15 to 16
CH1
18
18 to 19.2
CH1
28
28 to 30
CH1
5
5 to 5.3
CH1
12
12 to 12.8
CH1
24
24 to 25.6
CH1
48
48 to 51.2
CH1
5
5 to 5.3
CH1
12
12 to 12.8
CH1
17
17 to 18.19
CH1
36
36 to 38.4
CH1
24
24 to 25.6
CH1
15
15 to 16
CH1
15
15 to 16
Page 22 of 40
Adjustment
Output
range
Current (A)
35.29
25
20
16.7
12.5
36
30
19.3
80
65
30
15
110
90
63.5
29
62.4
50
66.4
Output
Hazardous
Power
Energy
(W)
600
Yes
600
Yes
600
Yes
600
Yes
600
Yes
540
Yes
540
Yes
540
Yes
400
Yes
780
Yes
720
Yes
720
Yes
550
Yes
1080
Yes
1080
Yes
1044
Yes
1200
Yes
750
Yes
996
Yes
260401-05 July 2019