Warning; Technical Data; Identification Label For The Silensys Range; Safety Devices - Tecumseh Silensys SILRG2432Z Notice D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 5

1- WARNING

Transport
For information regarding the delivery of condensing units,
please refer to our sales terms and conditions.

Installation

- This condensing unit and all related equipment must be
installed by qualified staff.
- The installation should be carried out in accordance with the
relevant refrigeration and electrical standards which apply in
that country. Refrigeration best practice must be followed.
- TECUMSEH EUROPE S.A. shall not under any circumstance
be liable if the installation and maintenance are not carried
out in accordance with the instructions given in this manual.

2-TECHNICAL DATA

■ 2.1. Identification label for the SILENSYS range
See Appendix 1, page 30
■ 2.2. Safety devices
All units are supplied with an adjustable HP / LP pressure
switch, with a 16 A maximum current rating and a isolator
lockable in the ON or OFF position as well as a thermal breaker
on the power circuit.
■ 2.3. Versions and options available
HP / LP pressure switch with manual reset - fusible plug on the
receiver – liquid line sight glass on the receiver fitted with a
fusible plug on twin fan models.
■ 2.4. Refrigeration schematic
See Appendix 2 , page 30, 31
3- INSTALLATION
■ 3.1. Unpacking
Before unpacking the unit, check that the packaging has not
been damaged in any way and that the exterior is in good
condition.
■ 3.2. Handling
The packaged condensing unit can be lifted by forklift or pallet
truck. The unit should therefore be kept in its packaging until it
has been moved to the installation site.
Once the packaging has been removed, Silensys units can be
moved or lifted either by forklift or straps according to the
model. Units must not be dragged into position.
■ 3.3. Location
Silensys® condensing units should not block or obstruct
thoroughfares, doors, shutters or the movement of personnel.
The surface supporting the condensing unit must be level and
capable of bearing the combined weight of the unit + support.
See table in Appendix 3, page 32 to 33 for condensing unit
weights.
Ensure there is sufficient distance between the condensing
unit and objects in the surrounding area to ensure good air
circulation.
See Appendix 3, pages 32 to 33
Silensys condensing units must be installed in well-ventilated
but not windy locations. Ensure there is good air circulation
to the condenser. There must be no obstacles in front or to
the side of the unit which would cause air recirculation to the
condenser. This will avoid among others an abnormally high
condensation temperature. The unit must be set up in a level
position and installed at an altitude not exceeding 2000 m.
| Installation Instructions
■ 3.4. Noise levels
Silensys condensing units have been designed to operate
extremely quietly.
Precautions must be taken during installation to avoid
generating additional noise and vibrations:
- Units must be securely mounted on a stable, rigid base,
- Connecting pipework must be sufficiently flexible to ensure
vibration is not transmitted to the rest of the installation.
We sometimes recommend isolating material be inserted
between the unit feet and the base or between the wall
mounting brackets and the wall. This can be either an isolating
pad or anti- vibration mounts (not supplied) conforming to
the manufacturer's recommendations for their selection and
installation. The selection of any anti-vibration products and
their potential for absorbing vibration is not the responsibility
of Tecumseh Europe.
■ 3.5. Mounting (1 or 2 options according to
model)
The unit must be installed and affixed on a level plane.
Ensure the unit is securely fixed to the type of floor or wall
surface upon which it is mounted using the appropriated
fixings (not supplied).
- Floor mounting
See Appendix 3, pages 32 to 33
Do not use wooden beams as a base onto which the product
is fixed. Create a concrete base strong enough to support the
load and vibration. Use fixing bolts which are of an appropriate
length and are capable of securing the product correctly.
Use the mounting kit supplied with the condensing unit.
- Wall mounting (single fan models only)
See Appendix 3, pages 32 to 33
Use the mounting kit supplied with the condensing unit.
Secure the product appropriately.
■ 3.6. Access to connections
See Appendix 4, page 34
■ 3.7. Refrigeration connections
To ensure the quality of our products, the condensing unit has
been dehydrated and charged with nitrogen.
On models fitted with suction tube diameter 1 1/8 or 1 3/8 the
suction line from the valve to the end of the tube is not under
nitrogen (the suction line is plugged and the valve closed).
COMPRESSORS
SUCTION VALVE
CAJ/TAJ
FH/TFH
114 to 126 Nm
TAG
114 to 126 Nm
VSA
114 to 126 Nm
RECEIVERS
0,75L to 9L
12L
DISCHARGE
VALVE
70 to 85 Nm
/
70 to 85 Nm
114 to 126 Nm
70 to 85 Nm
LIQUID START VALVES
70 to 85 Nm
114 to 126 Nm
366430 / 05.2015_d
9/46

Publicité

Table des Matières
loading

Table des Matières