94
REMARQUES
9) Mixing Humidity (AHU)
Output
Valid Range
SNVT_lev_percent
10) Filter Clean (AHU)
Output
Valid Range
NV
SNVT_switch
11) CO2 Concentration (AHU)
Output
Valid Range
12) VOC Concentration (AHU)
Output
Valid Range
Function
Using NV
Operation
NV
Function
Using NV
Operation
Field
value
state
Function
Using NV
Operation
NV
SNVT_ppm
Function
Using NV
Operation
NV
SNVT_ppm
Mixing Humidity display
network variable : SNVT_lev_percent, nvoMixRH
Mixing Humidity monitor
Operation
30 ~ 90 %
Filter Clean display
network variable : SNVT_switch, nvoFilter
Filter Clean monitor
Operation
not used (set in 0 % usually)
0 = OFF
CO2 Concentration display
network variable : SNVT_ppm, nvoSpaceCO2
CO2 Concentration monitor
Operation
0~2550 ppm
VOC Concentratio display
network variable : SNVT_ppm, nvoSpaceVOC
VOC Concentratio monitor
Operation
0~2550 ppm
1 = ON