Installation
AF-650 GP
[kW] / [HP]
0.25-0.37 /
0.33-0.5
0.75 / 1
1.5 / 2
2.2 / 3
3.7 / 5
5.5 / 7.5
7.5 / 10
11 / 15
15/18.5 /
20-25
22 / 30
30 / 40
37 / 50
Table 9.10 200-240 V
1) KTS fuses from Bussmann may substitute KTN for 240 V adjustable frequency drives.
2) FWH fuses from Bussmann may substitute FWX for 240 V adjustable frequency drives.
9
9
3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V adjustable frequency drives.
4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V adjustable frequency drives.
AF-650
GP
[kW] /
[HP]
0.37-0.75
/ 0.5-1
1.5-2.2 /
2-3
3.7 / 5
5.5 / 7.5
7.5 / 10
11 / 15
15 / 20
18.5 / 25
22 / 30
30 / 40
37 / 50
45 / 60
55 / 75
75 / 100
Table 9.11 380–480V
44
AF-650 GP Quick Guide
Recommended max. fuse
Bussmann
2)
Type JFHR2
FWX-5
FWX-10
FWX-15
FWX-20
FWX-30
FWX-50
FWX-60
FWX-80
FWX-125
FWX-150
FWX-200
FWX-250
Bussmann
Bussmann
Type RK1
Type J
KTS-R-6
JKS-6
KTS-R-10
JKS-10
KTS-R-20
JKS-20
KTS-R-25
JKS-25
KTS-R-30
JKS-30
KTS-R-40
JKS-40
KTS-R-50
JKS-50
KTS-R-60
JKS-60
KTS-R-80
JKS-80
KTS-R-100
JKS-100
KTS-R-125
JKS-125
KTS-R-150
JKS-150
KTS-R-200
JKS-200
KTS-R-250
JKS-250
Littel fuse
JFHR2
-
-
-
-
-
-
-
-
-
L25S-150
L25S-200
L25S-250
Recommended max. fuse
Bussmann
Bussmann
Type T
Type CC
JJS-6
FNQ-R-6
JJS-10
FNQ-R-10
JJS-20
FNQ-R-20
JJS-25
FNQ-R-25
JJS-30
FNQ-R-30
JJS-40
JJS-50
JJS-60
JJS-80
JJS-100
JJS-125
JJS-150
JJS-200
JJS-250
DET-759A
Ferraz-
Shawmut
4)
JFHR2
-
-
-
-
-
-
-
-
-
A25X-150
A25X-200
A25X-250
Bussmann
Type CC
KTK-R-6
KTK-R-10
KTK-R-20
KTK-R-25
KTK-R-30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Ferraz-
Shawmut
J
HSJ-6
HSJ-10
HSJ-15
HSJ-20
HSJ-30
HSJ-50
HSJ-60
HSJ-80
HSJ-125
HSJ-150
HSJ-200
HSJ-250
Bussmann
Type CC
LP-CC-6
LP-CC-10
LP-CC-20
LP-CC-25
LP-CC-30
-
-
-
-
-
-
-
-
-