Specifications
8 Specifications
8.1 General Technical Data
Line power supply:
Supply Terminals (6-pulse)
Supply voltage
Supply voltage
Supply voltage
Supply voltage
AC line voltage low / line drop-out:
During low AC line voltage or a line drop-out, the AF-650 GPdrive continues until the intermediate circuit voltage drops below
the minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated supply voltage.
Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency drive's lowest
rated supply voltage.
Supply frequency
Max. imbalance temporary between line phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ)
Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5kW/ 10HP
Switching on input supply L1, L2, L3 (power-ups) 11–75 kW/ 15–100HP
Switching on input supply L1, L2, L3 (power-ups) ≥ 90kW/ 125HP
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100kAIC RMS symmetrical Amperes, 240/480/600/690
V maximum.
Motor output (U, V, W):
Output voltage
Output frequency (75kW / 100HP and below)
Output frequency (90kW / 125HP and above)
Output frequency in flux mode
Switching on output
Ramp times
1)
Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
Starting torque (Variable torque)
Overload torque (Variable torque)
Torque rise time in advanced vector control (independent of fsw)
Torque rise time in flux vector control (for 5kHz fsw)
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4–5 x
torque rise time.
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
AF-650 GP Quick Guide
DET-759A
200–240V ±10%
380–480V ±10%
AF-650 GP 525–600V ±10%
AF-650 GP 525–690V ±10%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
near unity (> 0.98)
maximum 2 times/min.
maximum 1 time/min.
maximum 1 time/2 min.
overvoltage category III/pollution degree 2
0–100% of supply voltage
0.01–3600 sec.
maximum 160% for 60 sec.
maximum 180% up to 0.5 sec.
maximum 160% for 60 sec.
maximum 110% for 60 sec.
maximum 110% for 60 sec.
1)
18, 19, 27
L1, L2, L3
50/60Hz ±5%
8
8
0–1000Hz
1)
0–800
Hz
0–300 Hz
Unlimited
1)
1)
1)
1)
10ms
1ms
1)
4 (6)
1)
, 29
, 32, 33,
PNP or NPN
0–24 V DC
< 5 V DC
33