Some motors may be unable to run the complete
version of the test. In that case, select Reduced
Auto Tune
If an output filter is connected to the motor,
select Reduced Auto Tune.
If warnings or alarms occur, see 7 Warnings and
Alarm
4
4
4.5 Check Motor Rotation
Prior to running the adjustable frequency drive, check the
motor rotation.
1. Press [Hand].
2. Press [►] for positive speed reference.
3. Check that the speed displayed is positive.
When H-48 Clockwise Direction is set to [0]* Normal (default
clockwise):
4a. Verify that the motor turns clockwise.
5a. Verify that the Keypad direction arrow is
clockwise.
When H-48 Clockwise Direction is set to [1] Inverse (counter-
clockwise):
4b. Verify that the motor turns counterclockwise.
5b. Verify that the Keypad direction arrow is
counterclockwise.
4.6 Local Control Test
CAUTION
MOTOR START!
Ensure that the motor, system, and any attached
equipment is ready for start. It is the responsibility of the
user to ensure safe operation under any operational
condition. Failure to ensure that the motor, system, and
any attached equipment is ready for start could result in
personal injury or equipment damage.
NOTE
The Hand key on the Keypad provides a local start
command to the drive. The OFF key provides the stop
function.
When operating in local mode, the up and down arrows
on the Keypad increase and decrease the speed output of
the drive. The left and right arrow keys move the display
cursor in the numeric display.
1.
Press [Hand].
2.
Accelerate the drive by pressing [
Moving the cursor left of the decimal point
provides quicker input changes.
18
AF-650 GP Quick Guide
3.
4.
5.
If acceleration problems were encountered
If deceleration problems were encountered
See 7.4 Warning and Alarm Definitions for resetting the
drive after a trip.
NOTE
4.1 Pre-start through 4.6 Local Control Test in this chapter
conclude the procedures for applying power to the drive,
basic programming, set-up, and functional testing.
4.7 System Start-up
The procedure in this section requires user-wiring and
application programming to be completed. The following
procedure is recommended after application set-up by the
user is completed.
CAUTION
MOTOR START!
Ensure that the motor, system, and any attached
equipment is ready for start. It is the responsibility of the
user to ensure safe operation under any operational
condition. Failure to ensure that the motor, system, and
any attached equipment is ready for start could result in
personal injury or equipment damage.
] to full speed.
DET-759A
Note any acceleration problems.
Press [OFF].
Note any deceleration problems.
If warnings or alarms occur, see 7 Warnings and
Alarm
Check that motor data is entered correctly
Increase the ramp time in F-07 Accel Time 1
Increase current limit in F-43 Current Limit
Increase torque limit in F-40 Torque Limiter
(Driving)
If warnings or alarms occur, see 7 Warnings and
Alarm
Check that motor data is entered correctly
Increase the ramp time in F-08 Decel Time 1
Enable overvoltage control in B-17 Over-voltage
Control