E
- 55.514 -
INSTALLATION AND MAINTENANCE MANUAL
2008 - GEB0803LV
Contents
I.
I. IMPORTANT INFORMATION
I.1. Air heater
Heat exchanger Cu/ Al.-Serie 2000
Heating medium : hot water
Testing pressure : 20 Bar
Max. working pressure : 12 Bar
Max. work temperature : 110°C
Max. intake temperature : 40°C
Heat exchanger Cu/ Cu.-Serie 6000
Heating medium : hot water
Testing pressure : 20 Bar
Max. working pressure : 12 Bar
Max. work temperature : 110°C
Max. intake temperature : 40°C
Heat exchanger galvanised steel-Serie 1000
Heating medium : hot and overheated water, thermical oil
Testing pressure : 30 Bar, on request 40 Bar
Max. working pressure : 12 Bar
Max. work temperature : 260°C
Max. intake temperature : 40°C
Heat exchanger galvanised steel-Serie 3000
Heating medium : steam
Testing pressure : 30 Bar
Max. working pressure : 12 Bar
Max. intake temperature : 40°C
The heating medium may not be corrosive.
Motor 1 x 230 V 2 speed-Type 11
Motor 3 x 400 V 2 speed-Type 13
Motor 3 x 400 V 3 speed-Type 14
Motor 3 x 400 V Eex(e) 2 speed-Type 16
External rotor
Isolation class : F
The ventilators are balanced according the VDI 2060 norm, and are
equipped with a protection grille according to DIN 31001.
I.2. Application area
The Verco air heaters are suited for indoor mounting and the heating
of industrial halls, warehouses and show-rooms.
Any other use, or disregard of these specifications, is not allowed,
unless agreed otherwise. Any damage as aresult of an unauthentic
use, will be accounted on the entire responsability of the user.
The air heaters may not be mounted in explosion dangerous rooms,
outside, in humid rooms, in rooms with a high concentration of dust
or agressive atmosphere, or in rooms with high electromagnetics
demands.
I.3. Modifications
Without prefatory approval of the manufacturer, no modifications or
alterations can be made to the air heater.
AIR HEATERS
I.4. Qualified personnel
Installation, electrical connection and repair are only to be performed
by specialists. Transport and commissioning are only to be performed
by trained service personnel.
Failure to comply with the specifications given by the manufacturer
will invalidate the guarantee.
I.5. Transport and storage
Verco air heaters are packaged to comply with normal transport
requirements.
Transport and store the air heaters in the original packaging.
On delivery, inspect the package and the air heater.
In case of transport damage, the recipient should immediately
complain to the forwarding company and describe the damage on
the delivery note.
Compare the delivery note and the label on the air heaters.
The air heater must be stored in the original packaging in a dry area ,
and be protected against dirt and weather.
Avoid exposure to extreme cold or heat, above the 50°C,
temperatures. The heat exchanger can freeze open if temperatures
go below the freezing-point.
I.6. Safety instructions
The concerned safety prescriptions and the approved rules of
the technic should be followed in case of installation, electrical
connection and commissioning.
Power supply interrupted and secured.
Fan impeller has come to a stop.
Beware, after functioning, the air heater can be hot, also the
accessories and piping.
Apply personnel safety regulations : wear safety shoes and gloves,
and a work dress.
I.7. Guarantee
The guarantee on the air heaters, in case of normal use, is 10 years
on the heat exchanger, 2 years on the fan and 1 year on the electrical
equipment, after delivery date. The guarantee covers only the
replacement of the broken components with exclusion of all other
costs.
Are also excluded of the guarantee :
- corrosion damage
- damage due to wrong installation, connection or treatement
- when the client failed to fullfill his obligations towards Verco
In case of a complaint, mention the fabrication number, sticked on
the casing, to Verco.
I.8. Manufacturer
Our products are manufactured in compliance with applicable
international standards and regulations.
If you have questions regarding the use of our products, please
contact :
The manufacturer follows a politic of continuous improvement of his products,
and by these means attempts to make the needed adjustments to the products.
Therefore the manufacturer is entitled, without prior notification, to change a
component or characteristic of a product. This manual has the only purpose
Verco-Versichele N.V.
Karrewegstraat, 60 B- 9800 Deinze
Tel +32 -(0)9 / 386 48 46
Fax +32 -(0)9 / 386 83 63
E-mail : info@verco.eu
http://www.verco.eu