3 Scope of delivery

• 1 sensor
• 1 set of operating instructions

4 About This Product

The sensor is used to detect magnetic fields in explosive areas.

4.1 Product identification

Observe the product information on the product and packaging.
u

5 Assembly and Commissioning

REED
bn
bu
Illustration 1: Sensor porting configuration
1. Observe the Ex guidelines as per EN 60079-14.
2. The installation of electrical devices must be carried out in accordance with
applicable national regulations and performed or supervised by an electrical
specialist (in compliance with TRBS 1203 or equivalent).
3. Compare the information on the device with the information in the operating
instructions before installation.
Danger of injury if assembled under pressure or voltage
Assembling when under pressure or voltage can lead to injuries.
Make sure that all relevant system parts are not under pressure or voltage
u
before assembly.
4. Fit the sensor into the T-slot (any mounting orientation).
5. Install the sensor protected against mechanical impact and UV light (depend-
ing on the requirements/operating conditions).
6. Install cables with protection or provide for strain relief.

6 Care and Maintenance

The described sensors are maintenance-free.

7 Disposal

Dispose of the product in accordance with the national regulations in your
u
country.

8 Troubleshooting

Replace the sensor in the event of malfunctions or failure.
u

9 Technical Data

General
Voltage
AVENTICS
TM
ST6 | R412027659-BAL-001-AB | English
L+/M
M/L+
CAUTION
Ambient tem-
Voltage
perature
–20°C...+40°C 5...30 V DC
General
Switching current
Ambient temperature
Cable length
ATEX
Zone 2
Zone 22
Further technical data can be found in our online catalog at www.aventics.com.

10 Declaration of conformity

See the end of this document.
Switching
current
≤ 100 mA
Ambient tem-
Voltage
perature
–20°C...+50°C 5...30 V DC
–20°C...+60°C 5...30 V DC
R412027175
5 m
II 3G Ex ec IIC T4 Gc X
II 3D Ex tc IIIC T135°C Dc X
Switching
current
≤ 75 mA
≤ 50 mA