Magnetostrictive Linear Position Sensor – Rod Style
6
Calibration procedure
6.1
Calibration device (not for BTL7-...-S140)
The calibration device is an additional device for calibrating
the BTL.
► Before calibrating: Place the calibration device on the
connection side of the BTL.
► When finished with calibration: Remove the calibration
device to prevent changes.
► Keep the calibration device for later use.
Automatic deactivation!
If the buttons on the calibration device are not
pressed for approx. 10 min., programming
mode is automatically ended.
Button 1 (blue)
Fig. 6-1:
Calibration device in place
6.2
Programming inputs (not for BTL7-...-S135)
Instead of the calibration device, the programming inputs
may also be used for setting.
La corresponds to button 1,
Lb corresponds to button 2,
Programming input at 20 to 28 V (BTL7-_1_ _-...) or 10
to 30 V (BTL7-_5_ _-...) corresponds to button
depressed (high active).
Automatic deactivation!
If no signals are sent over the programming
inputs for approx. 10 min., programming mode
is automatically ended.
www.balluff.com
Button 2 (gray)
6.3
Calibration procedure overview
6.3.1
Teach-in
The factory set null point and end point is replaced by a
new null point and end point.
The detailed procedure for teach-in is described
on page 18.
Steps:
► Move magnet to the new zero position.
► Read new null point by pressing the buttons.
New null point
Fig. 6-2:
Reading new null point (offset shift)
► Move magnet to the new end position.
► Read new end point by pressing the buttons.
Before
After
New measuring length 100%
Fig. 6-3:
Reading new end point (changing the output gradient)
Before
After
New end point
english
15