Installation and Operation Instructions
EN
KWL Modbus RS 485 – Communication protocol
Confirguration data from the unit
Code MB
Address
Meaning
6/16/3
40000
Address KWL unit
40004
Factory setting
Operating information displayed on the operating unit
Code MB Address
Meaning
4
15000
Current operating status
15001
Volume flow outside air
15002
Volume flow outgoing air
15003
T – outside air
15004
T – before auxiliary heating
15005
T – after auxiliary heating
15006
T – extract air
15007
T – outgoing air
15008
Temperature frost protection
15009
Heating water temp. return
15010
Air quality
15011
Duct pressure supply air ductwork
15012
Unit status – 1
15013
Unit status – 2
15014
Pressure outside air (pre-filter)
15015
Pressure extract air (pre-filter)
15016
Pressure after outside air filter
15017
Pressure after extract air filter
15018
Output pre-heater
15019
Status bypass
15020
Output auxiliary heater
15022
Software – number
15023
Hardware – number
15024
Software – number – CM (motor)
Operating status
Code MB Address
Meaning
6/16/3
20000
Operation
20001
Nominal volume flow
20002
Nominal volume flow
20003
Temperature of the regulator or
room sensor
Direct regulation (operating mode 0x04)
Code MB Address
Meaning
6/16/3
20004
Output supply air fan
20005
Output extract air fan
20006
Output pre-heater
20007
Output bypass
20008
T – before auxiliary heating
20009
T – before auxiliary heating
20010
Cover flaps
20011
Units Start/Stop function
20012
Service Led
20013
Circulation pump WE
Range
<1;247>
<0;1>
CO
RH- <0;100>
LCKW-<0;50>
2
Unit
Factory setting
[-]
RESET is necessary after
hardware change
[-]
0
Range
Unit
<0;0x0B>
[-] (see Tab. 2)
<0;2000>
[m
<0;2000>
[m
<-40;100>
[°C]
<-40;100>
[°C]
<-40;100>
[°C]
<-40;100>
[°C]
<-40;100>
[°C]
<-40;100>
[°C]
<-40;100>
[°C]
-<0;2000>
[ppm]
2
[%]
[ppm]
<0;1000>
[Pa]
<0;FFFF>
[-] (s. Tab. 3.1 & 3.2)
<0;FFFF>
[-] (s. Tab. 4)
<0;1000>
[Pa]
<0;1000>
[Pa]
<0;1000>
[Pa]
<0;1000>
[Pa]
<0;100>
[%]
<0;100>
[%]
<0;100>
[%]
<0;FFFF>
<0;FFFF>
<0;FFFF>
Range
Unit
<0;5>
[-] (see Tab. 1)
<0;10000>
[m
<12;45>
[°C]
<-40;100>
[°C]
Range
Unit
<0;100>
[%]
<0;100>
[%]
<0;100>
[%]
<0;100>
[%]
<0;100>
[%]
<0;100>
[%]
<0;1>
OFF / ON
<0;1>
OFF / ON
<0;1>
OFF / ON
<0;1>
OFF / ON
/h]
3
/h]
3
[-]
[-]
[-]
/h]
3