OBO Bettermann V50-385 Série Manuel D'utilisation page 8

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
Installation instructions
• Clamp the protection device onto the hat rail,
ensuring that the lockable hat rail holder is un-
locked (Figure
).
2
• Maintain the stripping length and tightening
torque (Figure ).
• Connection according to the circuit diagram
(TN-C systems) or (TN-S / TT systems).
Dismantling
Figure :
• Unlock and remove arresters in the manner
shown.
• Open the hat rail holder with a flat screwdriver
and engage it (see also Figure
the protection devices.
Faults
If the integrated cut-off unit trips (e.g. due to age
on account of multiple, very high overvoltages),
the visual display (Figure
to red. In this case, remove the arrester and in-
sert a new arrester (available separately, V50:
item no. 5093 508, C50: item no. 5095 609). In
the case of devices with multiple arresters, it
must be assumed that the other arresters of this
device have experienced the same load. We rec-
ommend that you check them and, if necessary,
also replace them. Dispose of replaced arrest-
ers.
Remote signalling
Figure (only V50-..+FS..):
When at least one arrester is disconnected, the
changeover contact in the remote signalling mod-
ule switches from 11/12 to 11/14. Remote signal-
ling can be switched as an NO or NC contact.
This allows control of suitable signalling compo-
nents (e.g. central error messages, light or
acoustic signal).
• Connect the remote signalling cables as
shown, in so doing maintaining the specified
cable cross-section and the stripping length.
Maintenance
We recommend carrying out a visual check of
the visual display every 2-4 years or after light-
ning strikes.
Disposal
– Packaging as household waste
– Protection device/arrester as electronic waste.
Comply with the local waste disposal regulations.
OBO BETTERMANN GmbH & Co. KG
). Remove
2
) switches from grey
Technical data
V50 ... 385
IEC / DIN EN
Class I + II / Type 1 + 2
61643-11
U
385 V AC
C
U
N
U
P
1200 V
1 kA
8/20
U
@
res
1350 V
5 kA
8/20
I
12.5 kA
imp
I
30 kA
n
I
50 kA
max
I
SCCR
IP code
Number of
Ports
System
TN-, TT
Protection
L – PEN
path
L – N
Protection
L – PE
path
N – PE
x
F1 >160 A gL / gG
F1
+
F2
F2 ≤ 160 A gL / gG
F1 ≤ 160 A
F2
2
F1
gL / gG
1.5 – 35 mm
1.5 – 35 mm
1.5 – 35 mm
Accessories
a
a ≤ 15.5 mm (0.6 in)
3 x 16 mm
5012 010
V50-...-385
C50
255 V AC
230 V AC
≤ 1750 V
50 kA
50 kA
100 kA
50 kA
eff
IP 20 (built-in)
One-Port-SPD
TN-, TT (NPE)
-40 – +80 °C
-40 – +176 °F
5 – 95 %
N – PE
x ≥ 0 mm (0 in)
– (NPE)
– (NPE)
(AWG 16 – 2)
2
(AWG 16 – 2)
2
(AWG 16 – 2)
2
(3 x AWG 6)
2
EN
8

Publicité

Table des Matières
loading

Table des Matières