G
®
THERMASGARD
Resistance thermometer THERMASGARD
ture detection in larger rooms and halls. Due to the measuring method employed by this pendulum room
temperature sensor in combination with its positioning in the room, excellent and room-representative
measuring results are achieved as ambient air of the room is steadily washing around the sensor.
Resistance thermometer THERMASGARD
ture detection in larger rooms and halls, as dark radiation sensor for example. The pendulum room sensor
RPTF-2 (globe thermometer) determines the effective portion of active radiation or also the effective
radiant heat at the measured location. Due to the measuring method employed by this pendulum room
temperature sensor in combination with its positioning in the room, an excellent and room-representative
measuring result is achieved. The globe temperature is determined to take heat radiation into consideration
and to estimate the degree of thermal comfort (operative room temperature). The operative room
temperature describes the coaction of heat radiation and heat convection (the ratio of globe tempera-
ture ⁄ air temperature is approx. 70 % ⁄ 30 %).
TECHNICAL DATA
Measuring range:
Sensors ⁄ output:
Sensor protection:
Protective tube:
Globe:
Connection type:
Testing current:
Connection cable:
Insulating resistance:
Humidity:
Protection class:
Protection type:
®
THERMASGARD
RPTF
Type ⁄ WG03
RPTF 1 with metal sleeve
RPTF1 Pt100 PVC 1,5M
RPTF1 Pt1000 PVC 1,5M
RPTF1 Ni1000 PVC 1,5M
RPTF1 NiTK PVC 1,5M
RPTF1 LM235Z PVC 1,5M
RPTF1 NTC1,8K PVC 1,5M
RPTF1 NTC10K PVC 1,5M
RPTF1 NTC20K PVC 1,5M
RPTF 2 with globe
RPTF2 Pt100 PVC 1,5M
RPTF2 Pt1000 PVC 1,5M
RPTF2 Ni1000 PVC 1,5M
RPTF2 NiTK PVC 1,5M
RPTF2 LM235Z PVC 1,5M
RPTF2 NTC1,8K PVC 1,5M
RPTF2 NTC10K PVC 1,5M
RPTF2 NTC20K PVC 1,5M
ACCESSORIES
SF-M
Extra charge:
RPTF
®
RPTF 1 with passive output is specifically used for tempera-
®
RPTF 2 with passive output is specifically used for tempera-
RPTF 1 –5...+60 °C
RPTF 2 –5...+60 °C
see table, passive (optional also with two sensors)
RPTF 1 plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
RPTF 1 stainless steel V2A (1.4301), Ø = 16 mm, NL = 142 mm
RPTF 2
plastic, colour black, Ø = 50 mm
2-wire connection (4-wire connection optional)
< 0.6 mA (Pt1000)
< 1.0 mA (Pt100)
< 0.3 mA (Ni1000, Ni1000 TK5000)
< 2.0 mW (NTC xx)
400 μA...5 mA (LM235Z)
PVC, H03VV-F, 2 x 0.5 mm
2
KL = approx. 1.5 m (other lengths optional)
≥ 100 MΩ, at +20 °C (500 V DC)
< 95 % r. H.
III (according to EN 60 730)
IP 65 (according to EN 60 529)
Pendulum room temperature sensors
Sensor ⁄ Output
Pt100
(according to DIN EN 60 751, class B)
Pt1000 (according to DIN EN 60 751, class B)
Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K)
Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG - Ni1000
LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10
NTC 1.8 K
NTC 10K
NTC 20K
Pt100
(according to DIN EN 60 751, class B)
Pt1000 (according to DIN EN 60 751, class B)
Ni1000 (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K)
Ni1000 TK5000 (TCR = 5000 ppm ⁄ K), LG - Ni1000
LM235Z (TCR = 10 mV ⁄ K; 2.73 V at O °C), KP10
NTC 1.8 K
NTC 10K
NTC 20K
Metal sinter filter, Ø 16 mm, L = 32 mm, exchangeable stainless steel V4A (1.4404)
2-wire connecting leads, per running meter (PVC)
4-wire connecting leads, per running meter (PVC)
, ends stripped with wire end sleeves
RPTF 1 = Rev. 2021 - V24
RPTF 2 = Rev. 2021 - V15
1x two-wire connection
Standard
1x two-wire connection
LM 235 Z (KP 10)
1x four-wire connection
(optional)
Item No.
IP 65
1101- 6060- 1211-0 10
1101- 6060- 5211-010
1101- 6060- 9211-010
1101- 6061- 0211-0 10
1101- 6062- 1211-110
1101- 6061-2211- 010
1101- 6061-5211- 010
1101-6061- 6211- 010
IP 65
1101- 6070- 1211-0 10
1101- 6070- 5211-010
1101- 6070- 9211-010
1101- 6071- 0211-0 10
1101- 6072- 1211-010
1101- 6071-2211- 010
1101- 6071-5211- 010
1101-6071- 6211- 010
7000- 0050-2200- 100
on request
on request