NETWORKS AND CONNECTIVITY

CONNECTION TO SUPERVISION SYSTEM
(ERGO SOLUTION)
Using serial port RS485 it is possible to connect EVO
controllers (up to 247) to a management software that uses
standard MODBUS RTU as a communication protocol, with
the following characteristics:
settable baudrate (defualt: 9600);
no parity
8 bits of data
1 bit of stops
Inside a supervision network, each EVO controller acts as a
SLAVE towards the centralised management system which
constitutes the network MASTER (figure 01).
Once the network has been wired, it is necessary to configure
each EVO controller. Press PRG to access the MENU and then
enter sub-menu "Networks and connections" (password =
20). Set the SETUP RS485 parameters as follows:
MST/SLV = "Slave from SPV"
Protocol = "Modbus"
Serial address = set a value between 1 and 255
Speed = set based on the requirements of the Master
leave the SETUP OC PARAMETERS UNCHANGED (MST/SLV
= none).
For details on how to wire the network, read
"RS485 NETWORK GUIDE LINES" available in
the download area of the Galletti website.
The following functions are recognised and managed by the
controller as SLAVE:
CODE
DESCRIPTION
01
coil status reading
02
input status reading
03
holding register reading
04
input register reading
15
multiple coil status writing
16
multiple holding register writing
FC66003554
Rev 00
Controller for units
USER MANUAL
IT IS strictly forbidden to reproduce this manual, even partially
The following are the available variables:
COIL STATUS (DIGITAL READING/WRITING)
DESCRIPTION
1
ON/OFF controller
2
SUMMER/WINTER controller
3
ECONOMY controller
4
ENABLE ANTI-FREEZE controller
5
ENABLE ELECTRICAL HEATER controller
6
modulating ventilation MAN/AUTO controller
7
enable ON/OFF from MASTER
8
enable ECONOMY from MASTER
9
enable SUMMER/WINTER from MASTER
10
enable ANTI-FREEZE from MASTER
11
enable ELECTRIC HEATERS from MASTER
12
enable SETPOINT from MASTER
13
enable SETPOINT LIMITS from MASTER
14
enable VENTILATION SPEED from MASTER
15
KEYBOARD LOCK controller
INPUT STATUS (READ-ONLY DIGITAL)
DESCRIPTION
1
unit ON/OFF
2
SUMMER/WINTER
3
ECONOMY on
4
ANTI-FREEZE on
5
ALARM installed
6
Room temperature probe alarm
7
Water temperature probe alarm
8
Hot water temperature probe alarm
(only with 4-pipe units)
9
Room humidity probe alarm
10
Speed number (3/4)
11
Pipe number (2/4)
12
Type of ventilation (STEP/MODULATING)
13
Adjustment probe (DISPLAY/BOARD)
14
Installed electrical heaters
15
Installed humidity probe
16
Digital output 1 status (01)
17
Digital output 2 status (02)
18
Digital output 3 status (03)
19
Digital output 4 status (04)
20
Digital output 5 status (05)
21
Digital output 6 status (06)
22
Digital output 7 status (07)
EN
16