2 Change of the flow line [specialist]
1. Loosen the screw (1).
2. Take off the rotary knob (2) from the cock rod. Remove the adapter pieces (not shown)
for the extension of the plug axis, if necessary.
3. Loosen the two screws (3) and take off the cover (4).
4. Loosen the screws (5) and pull off the front plate (6).
5. Extract the sealing bush (7) with the cock plug (8) from the mixing valve body.
6. Loosen the screws (9) on the rear side of the mixing valve.
7. Press the cover (10) out of the mixing valve body.
8. Put the mixing valve cover in again on the other side of the mixing valve body and fix it
by using the screws (9).
9. Insert the sealing bush (7) with the cock plug (8) into the channel of the mixing valve.
Make sure that the o-rings are not damaged.
Only use a lubricant free of mineral oil (see previous page). Tighten the screws (8).
10. Screw down the front plate (7) using the screws (6).
11. Turn the cover plate (4) such that the designation PAW (see figure previous page) is on
the bottom and the scale is positioned according to the figure.
12. Screw down the cover plate (4) using the screws (3).
13. Put the rotary knob onto the cock rod. It depends on the length of the plug axis if you
need the adapter pieces (not shown) for the extension of the plug axis.
14. Fix the rotary knob (2) to the cock rod by using the screw (1).