12.3 Installer's Set-up Parameters

The various parameters that can be defined by the installer are
shown in the table below.
To access the installation parameters menu, scroll to AUTO, then
press (OK) for 10s.
Use (
) and (
) keys to highlight the parameter to be
adjusted.
Parameter
Name
dEG
Select temperature scale.
00:00
Select the hour format.
AIr
Calibration of the internal air sensor against the actual
(Air)
room temperature.
(The calibration must be done after 12 hours working at
the same set temperature).
AiPu
Fan pulse will switch on the fan for 30 seconds every
5 minutes. This will draw air over the air sensor if unit is
mounted where air circulation is restricted.
Nb vAL
Selection of the number of valves to be driven.
(2 Pipe
This parameter depends on the system design.
models only)
FAS SPEE
Allows the maximum fan speed to be switched off - the
unit will only run in Low and Medium speeds.
SetU
Select whether control is from the internal controls
system or from external BMS.
NIGt
Select option for fan speeds when the unit reverts to
night set back in cooling operation.
CLr ALL
Reverts the control back to factory settings.
End
Exit the installation menu.

12.4 building Management System Input Set-up

If the unit is integrated into a Building Management System,
control of the unit will be by BMS input only. The BMS
alternative setting from the parameters menu must be selected.
On the main screen the AUTO symbol will be turned off.
P1: Low fan speed input: P1 is indicated where the Room
temperature / set temperature is shown normally.
F1 is ON
P2: High fan speed input: P2 is indicated where the Room
temperature / set temperature is shown normally.
F3 is ON
20
Description
Press (OK) to toggle the parameter setting or edit the value.
If the value starts to blink, use (+) and (-) keys to adjust the value.
When the value is adjusted to the desired setting, press (OK)
to confirm.
Once parameters are set, go to <End> parameter and press (OK) to
go back to the main menu.

Default Setting

°C
24H
To adjust the air sensor temperature, enter the
measured temperature using the (-) or (+) keys.
To confirm the calibration, press (ok)
Press (+) and (-) keys at the same time to reset
the offset value.
YE5
(Yes)
0 valve
FA5
For Fast
AUt
(Auto)
NOr
(For Normal regulation)
Press (OK) for 5 seconds
P3: WINT MODE: Winter mode is used for system regulation.
Heating indicator flashes in this mode.
P4: SUMM MODE: Summer mode is used for system regulation.
Heating indicator flashes in this mode.
If the BMS inputs are wrong (e.g. P1 + P2 or P3 + P4), a message ERR
bMS will flash and the system stops BMS control.
Alternative Setting
°F
12H
NO
(No)
1 valve
NEd
For Medium
bN5
(For BMS)
AL1
(Fan speed 1 only)