Dimensions; Electrical Data - Purmo VIDO 1370071 Manuel D'installation, D'utilisation Et De Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

11.0 Technical Data
(continued...)

Dimensions

Nominal Height
Model
(mm)
600x800
600
600x1000
600
600x1200
600
600x1400
600
600x1600
600
Weight, Water Content and Motor Power
Motor
2 Pipe
Model
Power
Water
(W)
Content (i)
600x800
32
0.66
600x1000
35
0.92
600x1200
44
1.19
600x1400
53
1.45
600x1600
65
1.72
Note: 2 pipe water content = 2 pipe heating/cooling
or 4 pipe cooling and 4 pipe water content = 4 pipe heating.
Air Flow Rates
Fan
Condition
Speed
Normal
Heating
Medium
Boost
Normal
Cooling
Medium
Boost

Electrical Data

All VIDO models require an electrical supply of 220-240V 50Hz
fused at 3A.
16
Depth
Length
(mm)
(mm)
153
800
153
1000
153
1200
153
1400
153
1600
4 Pipe
2 Pipe
4 Pipe
Water
Unpacked
Unpacked
Content (i)
Weight (kg)
Weight (kg)
0.33
22.8
24.8
0.46
27.7
30.1
0.6
32.5
35.3
0.73
37.5
40.7
0.86
42.6
46.2
600x800
600x1000
90
135
148
221
247
370
65
98
110
165
202
302
Sound Levels
Sound Pressure (dBA) (at 2.5m)
Model
Normal
600x8000
24.8
600x1000
27
600x1200
24
600x1400
24.9
600x1600
27
Sound levels tested in accordance with ISO 3741.
Flow Rates/Pressure Losses
Flow
600x800 600x1000 600x1200 600x1400 600x1600
(l/h)
2 Pipe Heating/Cooling & 4 Pipe Cooling
100
0.7
150
1.4
2.1
220
2.9
4.1
330
6.1
8.5
500
13
17.8
750
27.5
36.5
100
1.4
150
2.8
4.2
220
5.8
8.2
330
12.2
17
500
26
35.6
Air Flow m
/h
3
600x1200
180
295
493
130
220
403
The VIDO should be sized based on "normal" outputs.
Medium
37.7
35.8
40.5
35.5
35
Pressure Loss (kPa)
1
1.4
1.6
2.9
3.2
5.5
6.1
11.1
12.2
22.9
24.9
46.2
49.8
4 Pipe Heating
2
2.8
3.2
5.8
6.4
11
12.2
22.2
24.4
45.8
49.8
600x1400
600x1600
225
270
369
443
616
740
163
195
275
330
504
605
Boost
47.9
47.9
51.7
54.8
56.3
1.9
3.7
7.1
14.2
28.7
57.1
3.8
7.4
14.2
28.4
57.4

Publicité