S+S Regeltechnik HYGRASGARD MODBUS Notice D'instruction page 14

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
HYGRASGARD
Function 04 Read Input Register
Register
3x0001
Temperature
3x0002
Temperature
3x0003
Relative humidity
3x0004
Relative humidity
3x0005
Dew point
3x0006
Absolute humidity
3x0007
Mixture ratio
3x0008
Enthalpy
Function 08 Diagnostics
The following sub function codes are supported
Sub Function
Parameter
Code
Echo of transmission data
00
(Loopback)
Restart Modbus
01
(Reset listen-only mode)
04
Activation listen-only mode
10
Delete counter
11
Counter bus telegrams
Counter communication errors
12
(Parity, CRC, frame errors, etc.)
13
Counter exception telegrams
14
Counter slave telegrams
15
Counter telegrams without answer
Function 17 Report Slave ID
Composition of answer telegram
Byte No.
Parameter
00
Number of bytes
01
Slave ID (device type)
02
Slave ID (device class)
03
Status
04
Version number (release)
05
Version number (version)
06
Version number (index)
MODBUS | Telegrams
Parameter
4 s sampling
Filtering
4 s sampling
Filtering
Computed value
Computed value
Computed value
Computed value
Data Type
Signed 16 Bit
– 350...+ 800
Signed 16 Bit
– 350...+ 800
Signed 16 Bit
0...1000
Signed 16 Bit
0...1000
Signed 16 Bit
0... 500
Signed 16 Bit
0... 800
Signed 16 Bit
0... 800
Signed 16 Bit
0... 850
Data Type
Answer
Echo data
Echo telegram
No answer
Echo telegram
Unsigned 16 Bit
All valid bus telegrams
Unsigned 16 Bit
Faulty bus telegrams
Unsigned 16 Bit
Error counter
Unsigned 16 Bit
Slave telegrams
Unsigned 16 Bit
Broadcast messages (address 0)
Data Type
Answer
Unsigned 8 Bit
6
Unsigned 8 Bit
6 = HYGRASGARD
Unsigned 8 Bit
20 = HYGRASGARD
Unsigned 8 Bit
255 = RUN, 0 = STOP
Unsigned 8 Bit
1...9
Unsigned 8 Bit
1...99
Unsigned 8 Bit
1
14
Value
Range
– 35 ... +80 °C
– 35 ... +80 °C
0 ...100 % r.H.
0 ...100 % r.H.
0 ...+50 °C
0 ... 80 g/m
0 ... 80 g/kg
0 ... 85 kJ/kg
®
MODBUS
®
/ HYGRASREG
3
®

Publicité

Table des Matières
loading

Table des Matières