Water Temperature Sensor Only; Factory Settings - Jaga BRIZA 12 Instructions D'installation

Masquer les pouces Voir aussi pour BRIZA 12:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

A.  WATER TEMPERATURE SENSOR ONLY
Configuration code : DPC.BR21 / DPC.BR22 / DPC.BR24 / DPC.BR25
ONLY DPC.BR24 /
MODE
DPC.BR25
A.1.  FACTORY SETTINGS
A.1.1.  Without control panel -
The unit is controlled by the water temperature The unit starts when the preset water temperature is
reached.
The unit starts when the water temperature > 28 ̊ C .
Only with configuration code DPC.BR22! The unit starts when the water temperature < 18 ̊ C .
1 Speed . The unit runs at the preset speed.
A.1.2.  With control pannel -
The user manually selects the desired mode via the control panel (
speeds. The unit starts when the preset water temperature is reached.
The unit starts at the last selected speed(1, 2 or 3), if the water temperature > 28 ̊ C .
The unit starts at the last selected speed(1, 2 or 3), if the water temperature < 18 ̊ C .
Off All functions are disabled until the user switches on the unit via the control panel.
-
-
3 speeds . The unit can run at 3 speeds.
38
1
24 V
+
GND
DPC.BR21 / DPC.BR22
DPC.BR24 / DPC.BR25
JAGA NV | BRIZA 12 - JDPC.002 | MANUEL | 05.07.2021 | V.08
[2]
4P
/
/Off). The unit can run at 3
2P

Publicité

Table des Matières
loading

Table des Matières