aldes DFE Compact micro-watt Manuel D'installation Et De Maintenance page 41

Centrale double flux haute efficacité
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.1.2.2 Operating LS mode with RC module master
Starting/stopping the fan is carried out with knobs I/III and OFF.
The assignment value for the supply constant airflow is a function of a 0-10V signal connected to terminals K2
and GND of the CBr. The link between voltage and airflow is linear. The exhaust constant airflow is equal to
%EXT/PUL of the supply airflow. (Except if 2 separate 0-10V signals are used to determine exhaust and supply
constant airflows, see advanced setup).
By pressing knob III of the RC you activate the pre-set multiplier (% on K3).
It is possible to start/stop the fans with an external contact connected to the CBr (see diagram hereunder).
Caution: terminals K1/K2/K3 of the CBr CANNOT be connected.
CBr
a) Wiring diagram with 1 CBr connected to 1 sensor
b) Wiring diagram with several CBr connected in parallel to 1 sensor
(*) K2
0-10V signal, maximum impedance allowed: 1500
Closed = fans OFF
Open = fans ON
Caution: use goldplated contacts only
(*)
41
+
+
0-10 Vdc (*)
0-10 Vdc (*)
-
-