Operation
3.7
exdirt / extwin
Properly install the draw-off tap at the devices.
3.8
exvoid / extwin
Comply with the following instructions:
•
For a hydraulic pressure test at the equipment, install a blind cover (to be supplied by the user) at the blow-off opening of the
venting mechanism.
•
To drain the released air or gases (odour), you may connect an additional hose or pipe at the ½" thread of the blow-off opening.
4
Operation
Note the following for operation:
•
The glycol portion of the water must be maximal 50 percent.
•
When dosing additives, comply with the manufacturer specification regarding the permissible dosing quantities. This is important
in particular to prevent corrosion.
•
Chemical additives such as inhibitors must be used only after an impact assessment in respect to all the materials used in the
system.
–
This impact assessment is the responsibility of the user.
•
Keep the system free from foaming substances. Foam or dirt beyond a specific portion can cause a temporary leaking at the venting
valve.
5
Maintenance
Caution – risk of burning!
•
Excessive surface temperatures in heating systems can cause skin to burn.
–
Wait until surfaces have cooled down or wear protective gloves.
–
The operator is required to attach corresponding warning notes in the device vicinity.
The time intervals for maintenance work depend on the specific operating conditions.
5.1
Pressure test
During a hydraulic pressure test, the pressure must not exceed 1.5 times the maximum working pressure.
5.2
Cleaning
5.2.1
Sludge separator
•
The cleaning interval depends on the accumulated dirt within the system.
•
Provide a catching container and a pressure and temperature-resistant drain hose, if required.
For cleaning, proceed as follows:
1. Gradually open the desludging valve for a short time until sludge no longer drains off.
–
Make sure that not much water escapes.
2. Subsequently, check the system pressure and add water as required.
10 — English
Reflex ex separator — 27.01.2014