5. Function
The EAQ 10/3 continuously measures the
concentration of gases and odours in the
room air (carbon monoxide, methane,
hydrogen, alcohol, tobacco smoke, dyes etc.)
and the air humidity in the room.
The value obtained from the VOC
measurement is used e.g. to control the
speed of fans (0-10 V output signal).
The potential-free switching contact can be
used to realise additional control functions,
e.g. switching the ventilation on/off if VOC
and/or humidity is present.
The switching points for the switching contact
are defined on the two VOC and RH
potentiometers – the function in question is
switched off when set completely to the right
Meaning of LEDs
Air quality,
blue:
good air quality
purple: acceptable air quality
*
red
:
poor air quality
* Remains lit up until the VOC
content has fallen sufficiently, e.g.
after smoke, coats of paint etc. have
been detected.
Relay switching status
green: contact element open
red:
contact element closed
Automatic brightness function
A sensor automatically sets the light
intensity of the two LEDs. These are
dimmed, e.g. at night.
VOC
4. Safety instructions and warnings │ UK

6. Technical data

Power
supply
Power
consumption
I
: Unit
max.
VOC sensor
element
Measuring
range for
VOC (unit)
Measuring
range for
humidity (unit)
Output
signal
Power
consumption
I
:
max.
Switching
contact
VOC switching
point
Humidity
switching point
Terminal
Degree of
protection
Weight
Dimensions
(L x W x H)

7. Ambient conditions

Permitted ambient temperature: 0...50 °C
Permitted humidity: 5...95 % RH
12 - 25 V AC or
12 - 35 V DC
14 mA (at 24 V)
Metal oxide sensor with
automatic calibration, takes
2 min. to warm up.
450 ... 2000 ppm / CO²
equivalent
5 ... 95 % RH
0 ... 10 V
0.5 A, 36 V AC/V DC
Ex factory approx.
1300 ppm / CO²
equivalent (± 500 ppm
can be set)
Ex factory approx. 50 % RH
(± 20 % RH can be set)
Plug with screw terminals
for 0.25...1.5 mm²
IP 30
0.078 kg
80 x 80 x 25 mm