If the torque values for a previous motorised movement have been stored in memory, these values
can be viewed in the next line for reference.
Example: in this example, the torque reading on the initial move-
ment was 12% and the torque on the most recent movement
is 18%.
The two values can be compared to determine whether any
preventive maintenance is required.
Storing motorised movement torque values
To save torque values for a motorised movement, select SAVE in the menu and then select:
torque => ref (yes).
Reference torque readings take the torque values for the most recent motorised movement.
If an error occurs, select: torque => ref (no) to restore the existing
reference torque values.
Values are only stored in memory when the user exits
the CHANGE menu confirms (change ok?)
Displaying the position / torque curve for the most recent motorised movement
Select torque curve in the torque menu and
turn to OK to confirm.
Select open or close movement and then turn
to OK to confirm.
The curve is shown on the display screen
with position from 0 to 100% and torque from
0 to 100% (100% is the maximum torque value
on the actuator nameplate)
19 CUSTOMIZING STATUS AND CONTROL INDICATIONS
19.1 LOCAL INDICATION
The local display can be configured as follows:
Invert display: the display can be inverted (rotated 180
degrees). Select Change in the menu, then signaling, then local
then invert display (yes).
Display torque: select this option to have the real-time torque
value displayed on the actuator display at the same time as the
position.
Select Change in the menu, then signaling, then local then
display torque (yes).
Red & Green LEDs: in the standard configuration, the red light indicates that the valve is closed and
the green light means it is open. The assigned colours can be changes so that the red light indicates
that the valve is open and the green one means it is closed.
Select change in the menu, then signaling, then local then lights: Red=(open)
To keep the valve open and valve closed labels in the correct position on the
indicator, you must also open the cover with the window and turn round the display indicator plate.
26
CLOSING%
18
ref.12
SAVE
torque => ref (no)
torque => ref (yes)
LOC INDICATION
return
opposite display
torque display
lights
return
Torque 60%
19.2 REMOTE INDICATIONS
Signals giving actuator status data are transmitted via bistable relays. Each relay can be configured
applying a list of available options.
INTELLI+ has four bistable relays in the standard configuration. A further three bistable relays can
be added as an option (the contact is open when there is no power).
The equipment is configured at the factory in accordance with the order.
Changes can be made as follows:
Select change in the MENU and turn to OK to confirm.
Select signaling in the CHANGE menu and turn to OK to confirm.
Select remote in the SIGNALING menu and turn to OK to confirm.
Select the relay in the SIGNALING menu and turn to OK to
confirm.
Choose contact type (i.e. activated contact status) and turn to
OK to confirm.
Choose function or functions required:
Several options can be selected for a single relay.
When an option is selected, the brackets are removed and an
asterisk * is displayed in front of the selected item. Turn to OK
again to cancel selection.
Liste
Details
*valve open
confirms valve open
(valve closed)
confirms valve closed
(torque limiter on opening)
torque limiter active on opening
(torque limiter on closing)
torque limiter active on closing
(indicates torque limiter action even if the valve is normally
closed on torque limiter)
(from x% to y%)
(1)
intermediate travel indication
(selector on local)
selector status
(selector on remote)
selector status
(selector on off)
selector status
(running)
(2)
actuator in running
(opening)
(2)
actuator performing opening action
(closing)
(2)
actuator performing closing action
(emergency command)
actuator has received an emergency command
(stop mid-travel)
actuator is halted (neither open nor closed)
(power on)
actuator powered normally
(thermal overload)
motor thermal relay tripped
(jammed valve)
movement could not be completed due to excessive torque
(lost phase)
phase missing on 3-phase supply
(lost signal)
4-20 mA signal lost (if positioner option active)
(handwheel action)
handwheel has been used since last motorised movement
(bus command)
if fieldbus option installed, this relay is assigned to an external
command.
(battery low)
If battery option used, the battery needs to be changed
(p.t. in progress)
A "partial stroke" test is in progress.
(p.t. fault)
A partial stroke operating error has occurred following start
of partial travel test, or it has not been possible to perform
test as the valve was not in the expected position.
REMOTE INDICATION
return
relay 1
relay 2
relay ...
RELAY 1
(closed contact)
(open contact)
RELAY 1
return
*valve open
(closed valve)
(torque limit open)
(...
27