Connection To The Chimney - Nordica AMERICA Instructions Pour L'installation, L'utilisation Et L'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

CHIMNEY CAPS - DISTANCES AND POSITIONING
Inclination of the roof
α α α α
15°
30°
45°
60°

6. CONNECTION TO THE CHIMNEY

An appliance with a constructive system 1 of the hearth door can be connected according to DIN 4705-part
3 to a flue, which has already been connected with other stoves or fireplaces, provided that the dimensions
of the chimney flue allows the connection.
For safety reasons the door of the appliances with constructive system 1, must be opened only for the
loading of the fuel or for removing the ashes, while during the operation and the rest, the door of the hearth
must remain closed.
The appliances with constructive system 2 must be connected to their own flue. The operating with open
door is allowed under supervision. The connection pipe to the flue must be the shortest possible, right, tight
and according to the current regulations.
The connection to the chimney must be performed with stable and strong pipes (we recommend a
thickness of 2 mm). The pipe for smokes exhaust must be fixed hermetically to the chimney. The diameter
inside the connection pipe must correspond to the external diameter of the smokes exhaust small trunk of
the stove. This is ensured by pipes according to DIN 1298.
ATTENTION: Eventual flammable pieces in the area of 20 cm round the connection pipes must be
changed with fireproof and not sensitive to heat materials.
For a good operation of the equipment it is essential that in the installation place it is introduced sufficient
air for combustion (see chapt. 7).
22
>A
H min.
(1)ridge axis
α
Distance between the roof
ridge and the stack
A (m)
< 1,85 m
> 1,85 m
< 1,50 m
> 1,50 m
< 1,30 m
> 1,30 m
< 1,20 m
> 1,20 m
> _ A
0,5 m
(2)roof
Minimum height of the stack (measured
0,50 m above the roof ridge
1,00 m from the roof
0,50 m above the roof ridge
1,30 m from the roof
0,50 m above the roof ridge
2,00 m from the roof
0,50 m above the roof ridge
2,60 m from the roof
UNI 10683/98
from the outlet)
H (m)
7096101 – Rev.05 – EN