F
LUSH MOUNTED INSTALLATION FOR
Dear Customer,
please read the following information carefully before using
the appliance for the first time for your own safety and to
ensure correct use and installation.
D
:
ESIGNATED USE
Indoor areas.
I
:
NFORMATION
• The Flush Mount Enclosure is an ideal way to neatly install
the heater into a ceiling. Flush mounting can be used with
any building grade ceiling materials.
• Maximum mounting heights should be strictly followed,
otherwise the performance of the units may be reduced.
The enclosure is manufactured from stainless steel.
WARNING:
Depending on material and design of ceiling structural
elements, the appliance must be secured with the
correct fasteners. The total weight of the heater and the
kit are up to 6 Kg, the installation location must be able
to hold 5 times the weight of the heater and the kit.
NOTE:
The bracket (no.2) is specially designed for flush-mounted
installation packed together with the frame (no.3). Please
don't use the bracket used for wall-mounted installation for
the flush-mounted installation.
Bracket for wall, or
ceiling installation
• Ensure all clearances detailed in the figure below are
strictly followed (dimensions in mm):
BRELGF1200
:
X
Bracket for flush-mounted
installation
• The minimum distance between the back of the enclosure
and any building material is 150 mm.
• The heater must not be located immediately below a
socket-outlet. The heater must not be located in front of a
socket-outlet.
• The socket must be located outside the physical footprint
of the units to minimize heat build-up behind the heater.
socket
• The minimum distance between the sides of the enclosure
and any support structure is 100mm.
The minimum distance between adjacent enclosures is
200mm.
GB
150mm Min.
Ceiling joist
Batten
100mm
Minimum