Installing The Grille; Types Of Control Cables - Mitsubishi Electric PMFY-P VBM-E Série Manuel D'installation

Masquer les pouces Voir aussi pour PMFY-P VBM-E Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 18
4. Electrical work
M1 M2
M1 M2
TB3
TB5
M1 M2
TB3

. Installing the grille

S
1
2
M1 M2
S
1
2
TB15 TB5
TB15
M1 M2
S
M1 M2
S
TB5
TB5
Fig. 4-3
Fig. 5-1
4.3. Types of control cables
1. Wiring transmission cables
Types of transmission cable
Shielding wire CVVS or CPEVS
Cable diameter
More than 1.25 mm²
Length
Less than 200 m
2. M-NET Remote control cables
Types of remote control cable Shielding wire MVVS
Cable diameter
0.5 to 1.25 mm²
Add any portion in excess of 10 m to within the
Length
longest allowable transmission cable length 200 m
3. MA Remote control cables
Types of remote control cable 2-core cable (unshielded)
Cable diameter
0.3 to 1.25 mm²
Length
Less than 200 m
4.4. Connecting remote controller, indoor and outdoor
transmission cables (Fig. 4-3)
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
• Install a remote controller following the manual supplied with the remote controller.
• Connect the remote controller's transmission cable within 10 m using a 0.75 mm
core cable. If the distance is more than 10 m, use a 1.25 mm
1 MA Remote controller
• Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
• DC 9 to 13 V between 1 and 2 (MA remote controller)
2 M-NET Remote controller
• Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller.
(Non-polarized 2-wire)
• DC 24 to 30 V between M1 and M2 (M-NET remote controller)
A Terminal block for indoor transmission cable
B Terminal block for outdoor transmission cable
C Remote controller
4.5. Setting addresses (Fig. 4-4)
(Be sure to operate with the main power turned OFF.)
• There are 2 types of rotary switch setting available: setting addresses 1 to 9 and
over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is "3", remain SW12 (for over 10) at "0", and match
SW11 (for 1 to 9) with "3".
2 How to set branch numbers SW14 (Series R2 only)
Match the indoor unit's refrigerant pipe with the BC controller's end connection
number.
Remain other than series R2 at "0".
• The rotary switches are all set to "0" when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
Note:
Please set the switch SW5 according to the power supply voltage.
• Set SW5 to 240 V side when the power supply is 230 and 240 volts.
• When the power supply is 220 volts, set SW5 to 220 V side.
A Address board
4.6. Sensing room temperature with the built-in sen-
sor in a remote controller (Fig. 4-4)
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the airflow at a time when the heating
thermometer is OFF.
.1. Checking the contents (Fig. -1)
• This kit contains the following parts.
Accessory name
Grille
1
Screw
2
Screw
3
2
junction cable.
Q'ty
Remark
1
6
M5 × 0.8 × 16
1
4 × 16
7
2

Publicité

Table des Matières
loading

Table des Matières