• Additional components are required to use this product.
• An earthing point is required for installation.
• This product requires no maintenance. However, please check it regularly for damage.
Replace damaged cables immediately.
• Always use the latest version of the operating instructions. You can find these and further
information at www.torqeedo.com, or scan the QR code on the back of these instructions.
•
power supply and secured against being switched on again throughout
the work.
• Allow hot components to cool before carrying out work on the system.
• Valid local regulations must be observed during installation!
• Contact protection must be provided for installation.
• Do not wear metallic jewellery during installation, and take care not to touch the
contacts.
• Follow the operating instructions for the other components!
• Do not connect any other electrical consumers to the fused circuit of the Torqee-
do system.
2. Scope of supply
See page 1, figures A1 – A3
• 1 x plus power cable 95mm² for connection to M8 busbar
• 1 x minus power cable 95mm² for connection to M8 busbar
• 1 x TorqLink feeder cable with integrated fuses for connection to M8 busbar
3. Operating conditions
Make sure that the operating conditions and the requirements for the energy source
(battery bank) and its fuse are observed.
Voltage level in volts (V)
Maximum battery current (permanent)
Maximum battery current (short-term)
Fuse load current cable*
Fuse TorqLink feeder cable with integrated
fuses
Cable cross-section for system earthing
**Fuse between the Torqeedo system and the battery bank
Before starting work, live parts must be disconnected from the
.
42.0 V – 58.8 V
240 A
280 A
350 A
2 A
Type: UL248-1.14
min. 50 mm²