Installing The Outdoor Unit; Installing The Refrigerant Piping; Precautions For Devices That Use R410A Refrigerant - Mitsubishi Electric Mr.SLIM PUHZ-HRP71HA2 Manuel D'installation

Masquer les pouces Voir aussi pour Mr.SLIM PUHZ-HRP71HA2:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 26

3. Installing the outdoor unit

M10 (3/8") bolt
Base
As long as possible.
Vent
Set deep in the ground
HRP71, 100, 125
HRP71, 100, 125
600
Min. 360
Min. 10
175

4. Installing the refrigerant piping

4.1. Precautions for devices that use R410A refrigerant

• Refer to 1.5. for precautions not included below on using air conditioners
with R410A refrigerant.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil
applied to the fl ared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.
Always apply no-oxidation brazing when brazing the pipes, otherwise, the
compressor will be damaged.
600
175
950
Fig. 3-1
(mm)
• Be sure to install the unit in a sturdy, level surface to prevent rattling noises
during operation. (Fig. 3-1)
<Foundation specifi cations>
Foundation bolt
Thickness of concrete
Length of bolt
Weight-bearing capacity
• Make sure that the length of the foundation bolt is within 30 mm of the bottom
surface of the base.
• Secure the base of the unit fi rmly with four-M10 foundation bolts in sturdy loca-
tions.
Installing the outdoor unit
• Do not block the vent. If the vent is blocked, operation will be hindered and
breakdown may result.
• In addition to the unit base, use the installation holes on the back of the unit to
attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 ×
15 mm or less) and install on site.
Warning:
• The unit must be securely installed on a structure that can sustain its
weight. If the unit is mounted on an unstable structure, it may fall down
and cause damage or injuries.
• The unit must be installed according to the instructions in order to mini-
mize the risk of damage from earthquakes, typhoons, or strong winds. An
incorrectly installed unit may fall down and cause damage or injuries.
HRP200
HRP200
600
Warning:
When installing or moving the air conditioner, use only the specifi ed refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig-
erant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.
Pipe size (mm)
[6.35 [9.52 [12.7 [15.88 [19.05 [22.2 [25.4 [28.58
Thickness (mm)
0.8
• Do not use pipes thinner than those specifi ed above.
• Use 1/2 H or H pipes if the diameter is 19.05 mm or larger.
M10 (3/8")
120 mm
70 mm
320 kg
Min. 460
600
225
225
Min. 10
1050
0.8
0.8
1.0
1.0
1.0
1.0
1.0
5

Publicité

Table des Matières
loading

Table des Matières