NV300 Handbook
3.
Unit without global option, high current channel 2 de-rated to 19A
4.
Unit without global option, low current channel 2 de-rated to 13A
Additional variations and limitations of use for all fan version:
1. Channel 4 - 3H, 5H, TH and FH max output current 1.5A.
The products listed in the following table are typical examples:
Model
NVA3-453FFH
NVA3-453HFHFH-N3
NVA3-4GFGT-N5
Custom models:
Model: NVA3 4G5HFHFH-N3-I (Y30006# where # can be any letter except A)
Maximum outputs: CH1:24V, 6A. CH2:5V, 6A. CH3:15V, 3A. CH4:15V, 0.5A.
Maximum ambient: 50°C
Orientation: Horizontal
Comments: Reverse air, compliant with 60950-1 only.
Model: NVA3 4G5HFHFH-N3-I (Y30006A)
Maximum outputs: CH1:24V, 6A. CH2:5V, 6A. CH3:15V, 3A. CH4:15V, 0.5A.
Maximum ambient: 40°C
Orientation: Horizontal
Comments: Reverse air, 8.2Vdc fixed speed fan, compliant with 60950-1 only.
Customer Air Cooling (option C, U and open frame):
The following method must be used for determining the safe operation of PSUs.
The components listed in the following table must not exceed the temperatures given. To determine the component
temperatures the heating tests must be conducted in accordance with the requirements of the safety standard in
question.
Test requirements include: PSU to be fitted in its end-use equipment and operated under the most adverse
conditions permitted in the end-use equipment handbook/specification and which will result in the highest
temperatures in the PSU. To determine the most adverse conditions consideration should be given to the end use
equipment maximum operating ambient, the PSU loading and input voltage, ventilation, end use equipment
orientation, the position of doors & covers, etc. Temperatures should be monitored using type K fine wire
thermocouples (secured with cyanoacrylate adhesive, or similar) placed on the hottest part of the component (out of
any direct airflow) and the equipment should be run until all temperatures have stabilised.
Minimum 0.5m/s airflow for customer air cooling.
CH1
CH2
5V/40A
3.3V/15A
5V/40A
3.3V/24A
24V/12.5A
15V/10A
CH3
CH4
15V/5A
-15V/2A
15V/8A
-15V/2A
24V/2.5A
-12V/1A
Page 16 of 25
Global
Option
-
5V/2A
13.5V/1A
17173 issue 14, October 2018