Menu: Cooling; Menu: Hot Water - Daikin RoCon+ HP1 ETSH16P30D Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 117
7
Parameter settings
Parameters
Setting range
Min / Max
Comfort heat-
ing
Off
On
Tab. 7-15 Parameter in the "Heating" menu
7.6.4

Menu: Cooling

[→ Main menu → Configuration → Cooling]
Parameters
Setting range
Min / Max
Target flow
5 – 25 °C
cooling, start
Target flow
5 – 25 °C
cooling, max.
Start cooling
15 – 45 °C
outside temp.
Max. cooling
20 – 45 °C
outside temp.
Feed temper-
5 – 25 °C
ature lower
limit
Feed temper-
8 – 30 °C
ature, cooling
mode
Cooling set-
-5.0 – +5.0 K
point correc-
tion
Interlink tem-
1 – 50 K
perature re-
duction
Tab. 7-16 Parameter in the "Cooling" menu
7.6.5

Menu: Hot water

[→ Main menu → Configuration → DHW]
Parameters
Setting range
Min / Max
Max. hot water
10 – 240 min
loading time
Operating Instructions
40
Description
If the heat pump cannot cover the heating demand when outside temperat-
ures are very low, heat is extracted from the storage tank and used for
room heating (see
Chap.
4.5.4)
Only if the heating demand is not covered is the storage tank temperature
raised. During the time it takes to raise the temperature, there may be a
slight loss of comfort.
At corresponding outside temperatures, the storage tank temperature is al-
ways raised above the storage tank temperature set for the hot water re-
quirement. The power consumption of the heat pump may increase.
Description
Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the cooling feed target temperature at the start of cooling mode
(outside temperature = [Start cooling outside temp.] parameter)
Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the minimum cooling feed target temperature. This is held con-
stant as of the outside temperature ([Max. cooling outside temp.] para-
meter).
Only if [Weather-compensated] parameter = Weather-compensated:
Setting as of which outside temperature cooling mode starts with the
highest cooling feed target temperature [Target flow cooling, start] (setting
condition: "Cooling" operating mode).
Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the outside temperature at which the lowest cooling feed target
temperature [Target flow cooling, max.] is specified (setting condition:
"Cooling" operating mode).
Setting of the absolute lower limit of the cooling feed target temperature.
Limitation acts if a lower cooling feed target temperature is determined
from other parameter settings.
If optional frost protection valves are installed in the system, the [Feed tem-
perature lower limit] parameter must not be set below 7 °C.
Only if [Weather-compensated] parameter = Feed temperature, fixed:
Setting of the cooling feed target temperature (fixed value) for active cool-
ing mode.
Parallel shift of the cooling characteristic curve by the set value.
Only if [Interlink function] parameter = On:
When the RT switching contact cooling is closed, the cooling feed target
temperature is reduced by the set value (see [Interlink function] para-
meter). Request, e.g. by HP convector.
Description
Setting of the maximum duration of a domestic hot water preparation cycle.
Then cancellation of domestic hot water preparation if the current hot water
temperature does not reach the set target value in the [Hot water temperat-
ure target 1] parameter.
Factory
Incre-
Access
setting
ment
BE HF
N
E
Factory
Incre-
Access
setting
ment
BE HF
18 °C
1 °C
E
E
8 °C
1 °C
E
E
24 °C
1 °C
E
E
35 °C
1 °C
E
E
18 °C
1 °C
N
E
18 °C
1 °C
E
E
0.0 K
1 K
N
E
5 K
1 K
N
E
Factory
Incre-
Access
setting
ment
BE HF
60 min
10 min
N
E
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN