Parameter settings
Parameters
Setting range
Min / Max
Bivalence
function (*)
Aux. heating al-
ways possible
Aux. heating T-
biv. dependent
Bivalence tem-
-15 °C – +35 °C Setting influences the effect of the potential-free AUX switching contact
perature
Tab. 7-10 Parameter in the "External heat source" menu
7.5.4

Menu: Inputs/Outputs

[→ Main menu → Settings → Inputs/Outputs]
Parameters
Setting range
Min / Max
Smart grid
Off
On
Smart grid
mode
Comfort
Standard
Eco
HT/NT func-
tion
Inactive
Switch off com-
pressor
Switch off com-
pressor + BUH
Switch all off
HT/NT contact
Normally open
contact
Normally closed
contact
Operating Instructions
34
Description
The bivalence function is only relevant to operation of the optional heater
booster due to a backup request (room heating mode).
Operation of the backup heater is always possible.
Backup heater is only released if the temperature set in the [Bivalence
temperature] parameter is undercut.
(toggle switch output A) defined in the [AUX switching function] parameter.
Only if [Bivalence function] parameter = heating up T-bivalence:
Outside temperature as of which the optional heater booster is activated to
support room heating. The bivalence temperature is relevant to operation
of the optional heater booster due to a backup request (room heating
mode). The temperature of the temperature sensor (information value
Temperature
) integrated in the heat pump outdoor unit is used for this.
A
Description
Evaluation of the SG signal (see
Smart Grid function not active, SG signal is not evaluated.
Depending on the utility company signal, the heat pump is shut off (no frost
protection function) or operated at higher temperatures.
Only if [Smart grid] parameter = On:
Is used for a possible target temperature increase with a Smart Grid
switch-on command.
Increase of the hot water target temperature by 5 K
Increase of the feed target temperature by 2 K and increase of the hot wa-
ter target temperature by 5 K
Increase of the feed target temperature by 5 K and increase of the hot wa-
ter target temperature by 7 K
Setting of which heat sources are switched off if the high rate signal output
by the utility company (EVU) is received in the case of a low rate mains
connection.
Deactivated (no effect)
Refrigerant compressor is switched off
Refrigerant compressor and backup heater are switched off
Everything is switched off (no frost protection function, see
Definition of whether the HT/NT input is evaluated as a normally closed
contact or a normally open contact.
Switching contact closed during high rate.
Switching contact closed during low rate.
Chap.
4.4).
Chap.
Factory
Incre-
setting
ment
-
0 °C
1 °C
Factory
Incre-
setting
ment
-
-
-
4.5.3)
-
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN