Guide to quick standard set-up
menu items
to
A
H
These instructions refer to the menu items
As the interface/repeater unit is installed, these menu
items are shown automatically and in alphabetical order
in the display.
In many cases, the factory settings are sufficient and
the interface/repeater unit can be used without further
settings being programmed. When using the factory set-
tings, first confirm the settings in menu items
F
and
G
(described on pages 16-21).
Then continue in menu item
, submenu "Register prod-
H
ucts" (described on pages 22-25) and submenu "Select
products" (described on pages 26-27). It is not necessary
to go through the other submenus in menu item
The interface/repeater unit is now ready for use.
12 VELUX
A B
A
to
H
.
XXXXXXX XXX
XXXXXXX
XXXXXXX
Enter
,
,
,
C
D
E
.
H
ENGLISH
Example of typical use of the interface/repeater unit
thermostatic control of a vELUX skylight by a
compatible thermostat
C
D E F G H
A thermostat can be used to control automatic opening
and closing of skylight(s) depending on the temperature. A
typical thermostat works by means of a dry change-over
Back
contact that switches between two positions depending
on the ambient temperature.
The illustration shows how to connect the dry change-
over contact to the interface/repeater unit.
A thermostat set to 72°F/22°C will typically change
position (ie open the skylight(s)) when the temperature
rises above 74°F/23°C, and switch back (ie close the
skylight(s)) when the temperature has again fallen below
70°F/21°C.
The skylight(s) can be operated with the remote control
at any time.
~74°F/
23°C
ENGLISH
C
˚F
72°F/
22°C
~70°F/
21°C
VELUX 13