Technical Data; Plug And Socket Ghg 521 - Cooper Crouse-Hinds CEAG GHG 521 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Dimensions in mm
X = fixing dimensions
Wall socket swithable by plug 2 pole+PE
Wall socket w/o switch 3-pole
Wall socket w/o switch 4-pole
Wall socket w/o switch 5-pole
Wall socket with switch 4-pole
Plug 3-pole
Plug 4-pole
Plug 5-pole
Dim.
Flange socket 3-polig
109 75 72
Flange socket 4-polig
111 72 76,5
Flange socket 5-polig
111 75 84
Plug and socket system 16A, GHG 521
1

Technical data

1.1

Plug and socket GHG 521

Rated voltage:
2-pole+PE
3-pole+PE
3-pole+N+PE
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity:
Wall socket 2-pole + PE, switchable by switch 250 V / 16 A
Switching capacity:
Wall socket 3-pole + PE, with switch
Perm. ambient temperature:
(Special versions permit deviating temperatures)
Perm. storage temperature in original packing:
Protection category acc. to EN 60529 / IEC 529
with closed and secured hinged cover:
Insulation class acc. to EN/IEC 61140:
Cable entries:
Wall socket with switch
Dim. A
Wall socket without switch
163
Plug / Coupler 2-pole + PE:
160
Plug / Coupler 3-pole + PE:
159
Plug / Coupler 3-pole + N + PE:
Supply terminal:
Wall socket with switch
Wall socket without switch
Flange socket
Coupler
Plug
Test torques:
Cap nut of the M 25 entry
Cover screws
Terminals
Terminals
Self-cutting screws size 4
Self-cutting screws size 5
Switch connection screw
Weight:
Wall socket without switch
Wall socket switchable
Plug
Flange socket
Inlet
Coupler
Wall socket without switch
Wall socket with switch
Plug
Flange socket
Inlet
Coupler
Wall socket without switch
Plug
Flange socket
Coupler
A
B
C
Wall socket
Flange socket
Inlet
Coupler
Plug
2-pole+PE
2-pole+PE
2-pole+PE
2-pole+PE
2-pole+PE
2-pole+PE
3-pole+PE
3-pole+PE
3-pole+PE
3-pole+PE
3-pole+PE
3-pole+PE
3-pole+N+PE GHG 521 25
3-pole+N+PE
3-pole+N+PE
3-pole+N+PE GHG 521 35
Inlet, 3-pole
up to 500 V, 50/60 Hz
up to 690 V, 50/60 Hz
up to 690 V, 50/60 Hz
max. 16 A
max. 16 A
max. 35 A gL
AC 3
AC 23
AC 22
500 V / 20 A
500 V / 25 A
690 V / 11 A
690 V / 25 A
-20°C up to +40°C (catalogue version)
-55° C to +80° C
IP 66 (catalogue version)
I - is complied with by the devices
(catalogue version)
1 x M25 (Ø 8 - 17 mm) + 1 x blanking plug
4 x drilling M20 (2 x top, 2 x bottom)
Ø 8 - 19 mm
Ø 8 - 21 mm
Ø 12 - 21 mm
Cross section
Stripped wire length
2 x 0.75 - 6 mm²
6 mm
2 x 1.50 - 6 mm²
10 mm
2 x 1.50 - 6 mm²
10 mm
2 x 1.50 - 6 mm²
10 mm
1 x 1.50 - 6 mm²
10 mm
3.5 Nm
2.5 Nm
2.5 Nm
2.5 Nm
2.5 Nm
2.5 Nm
1.5 Nm
2.0 Nm
3.0 Nm
0.8 Nm
(catalogue version)
GHG 521 23
approx. 0.80 kg
GHG 521 43
approx. 1.10 kg
GHG 521 73
approx. 0.32 kg
GHG 521 83
approx. 0.37 kg
GHG 521 93
approx. 0.26 kg
GHG 521 33
approx. 0.48 kg
GHG 521 24
approx. 0.85 kg
GHG 521 44
approx. 1.60 kg
GHG 521 74
approx. 0.39 kg
GHG 521 84
approx. 0.42 kg
GHG 521 94
approx. 0.31 kg
GHG 521 34
approx. 0.54 kg
approx. 0.90 kg
GHG 521 75
approx. 0.42 kg
GHG 521 85
approx. 0.47 kg
approx. 0.55 kg
Inlet, 4-pole
Cooper Crouse-Hinds GmbH
7 7 7 7 7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ceag ghg 521 44Ceag ghg 521 74

Table des Matières