Function and features
The AS-i slave converts analogue signals (temperature values) into dig-
ital values and transfers them to the host.
The data transfer is asynchronous according to the AS-i profile S-7.3
and the AS-i specification V2.1.
• Sensor supply from AS-i
• Conversion of measured values for 4 channels: 480ms
• Resolution 0.1°C
• Measuring range -200 .. +850°C
• AS-i profile S-7.3.E
• The actuators are connected via Combicon connectors (accessories,
e.g. E70230)
• Connection of 2-wire / 4-wire sensors possible
• Maximum number of modules per AS-i system: 31
Installation
Fix the module onto a 35mm rail.
25
105
LEDs
addressing plug
Combicon connector with screw termials (optional)
8
PAGE