emmeti TM3 Mixing Unit Manuel D'installation Et D'utilisation page 13

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. BalaNCINg aND SETTINg THE SYSTEM
3.3.2
Lockshield adjustment with built-in
flow-rate meter (if there is one)
1
2
Measurement range: 0-4 l/min
Maximum operating pressure:
6 bar
Max. operating temperature:
90°C
Kv = 0.15 (1 l/min) - 0.55 (4 l/min)
Kv max (out of measurement range) = 0.9
Accuracy: ±10% fs
fs = End of scale
The adjustment is carried out as follows:
1. Manually turn ring nut , anticlockwise until the lockshield is fully open
(max 4 turns).
2. Lower ring nut  and calibrate using regulator  until you reach the
correct flow rate (indicated directly on the meter).
3. Lift ring nut  until you hear it clicks, which means it has been positioned
correctly.
PLEASE NOTE: All the steps above must be carried out manually.
It is also possible to lead seal the collar in the reached position, using the
holes in flaps  to fasten it:
– directly to the manifold, thus preventing any tampering
– to the meter, leaving the possibility to shut-off the way without modifying
the set maximum opening calibration.
Cleaning of the glass
– Turn ring nut  clockwise until the lockshield is completely closed
– Remove the glass slide by unscrewing it from regulator  with the CH17
box spanner(*).
– Clean the glass slide and screw it back onto regulator .
– Turn ring nut  anticlockwise until the lockshield is fully open (max
4 turns).
Graph with flow-rate meter pressure drops (0÷4 l/min)
*
3
= No. of turns to open the flow-rate meter
Graph with pressure drops (0÷4 l/min) of the flow-rate meter in
the fully open position
300
250
200
150
100
TA Regulator fully open
LP Meter limit
Q [l/h]
50
0
0
60
120
180
Q [l/h]
GB
GB
LP
TA
240
300
360
13

Publicité

Table des Matières
loading

Table des Matières