3. BalaNCINg aND SETTINg THE SYSTEM
By setting the bypass to 1, a 1032 l/h flow rate corresponds to a 90 mbar
pressure drop (0.09 bar).
Assuming that ΔP pav = floor-mounted system pressure drop = 0.25 bar,
set the capacity of the Wilo Yonos PARA circulator in order to sure a flow
/h) and a head H = ΔP valv + ΔPpav = 0.09 + 0.25
rate of 1032 l/h (1.03 m
3
= 0.34 bar (≅ 3.4 m CA).
Here below are some tables that report the data for systems selected based
on the requested heating capacity.
Therefore, first use the table or formulas to carry out the setting and then
use the thermometers to make sure the project temperatures of the fluid
are actually reached.
To increase the ΔT of the floor circuits, just reduce the bypass flow rate.
ΔTip = 10 °C T Boiler = 70 °C Tip = 45 °C
Capacity (W)
Circulator
setting
18000
maximum
17000
maximum
16000
maximum
15000
maximum
14000
maximum
13000
average
12000
average
11000
average
10000
average
10
Tc
Qby-pass
Tr
ΔPip = 0,25 bar
ΔTip = 5 °C T Boiler = 70 °C Tip = 45 °C
Bypass
setting
5
3 - 4
2
1
0
5
4
2 - 3
1
Tip
Tr
Capacity (W)
Circulator
setting
9000
maximum
8000
maximum
7000
maximum
6000
average
5000
average
4000
average
GB
GB
Qip
ΔPip = 0,25 bar
Bypass
setting
5
2 - 3
0
5
2 - 3
0