Technical Characteristics; Function And Description; Led Indicator - Watts Master 6 zones 24VAC Guide Utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 6
1.

Technical characteristics

Operating temperature
Protection
Power supply
Fuse
Outputs
2.

Function and description

The UFH-MASTER with 6 zones is a wiring module with built in pump logic. All the main electrical connections
for water floor heating system are existing. This box can be adapted either on a DIN rail or directly on a wall.
(the DIN rail mounting permit to add with facility a UFH-SLAVE or UFH-H&C module).
It connects room thermostats to their corresponding actuators.
The state of each zone is indicated by individual green LED.
As soon as we have a heat demand from one zone a relay with 2 potential-free contacts is switch on (pump,
boiler or other possible connection).
By using terminal A and B, the pilot wire of thermostats can be controlled by a main zone programmer (UFH-
DIGITAL PROGRAMMER 24V).
3.

LED indicator

Red:
- Heating indication (water circulation on this zone)
Screw connector for pump
and accessories
4.
Possible combinations (6, 10, 12 zones)
MASTER 6 ZONES
MASTER 6 ZONES
MASTER 6 ZONES
0°C - 50°C
Class I - IP20
24 VAC +/- 10%
2.5AT 5x20mm
Pump & accessories:
Relay => 2 free contact 8A 250Vac
Zones:
6 independent zones => The maximum output power of each zones depends
of the thermostat connecting on this zone but for easy installation we
recommend a maximum of 4 actuators by zones.
LED indicator zone
Screw connector for
power supply
+
SLAVE 4 ZONES
+
SLAVE 6 ZONES
4
Supply for thermostat and
actuators for 1 zone