Advanced Menu; Pressure Sensor Calibration - Coelbo DIGIPLUS Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ADVANCED MENU

- Press simultaneously
- By mean of
or
- Press
for validation.
- The parameters sequence is:
TYPE
SYSTEM REACTION
Activation of the automatic restore
Ar0
Ar1
system ART (Ar1) o disable (Ar0).
In case of enabled ART, it can be
set the number of restore at-
n01
n48
tempts, between 1 and 48.
It can be set the span of the at-
t10
t40
tempt between 10 and 40 seconds.
Stand-by disabled (Sb0) or
Sb0
Sb1
enabled (Sb1)
Restore factory settings (rs1)
rs0
rs1
With PF1 is activated the pressure
dependent mode with start and
PF0
PF1
stop pressures.
With P_ON is activated a mini-
mUM working pressure. Under
P0.0 P_ON
this pressure is activated an alarm
(A11).
Time, in seconds, under minimal
t05
t99
pressure necessary to activate A11.
Restore factory settings (rs1)
rs0
rs1

PRESSURE SENSOR CALIBRATION

In case of wrong lecture of the pressure sensor it can be
adjusted again.
For the pressure sensor calibration is necessary to have a
pressure gauge in the installation. Proceed following next
steps:
ZERO REGULATION
1.
Open the taps living the hydraulic net without pressure.
2.
Press simultaneously the buttons
display show 0.0 flashing.
3.
Press
to validate.
FULL SCALE
1.
Start the pump until cut-out of the pressure switch.
2.
Press simultaneously the buttons
play flashes with a figure.
3.
Adjust the pressure with the arrows push-buttons to get
the pressure desired.
4. Press
to validate.
Remark: pressure sensor decalibration should not be
a normal event. If it is frequently repeated contact the
technical service.
+
+
+
+
during 5 seconds.
the values can be changed.
and
and
WARNINGS AND ALARMS
COD. ALARM
O
FACTORY
SETTING
Ar1
A01
48
( ( O ) )
15"
0
rs0
0
0.0
A11
( ( O ) )
05
rs0
O
A02
( ( O ) )
until the
A05
O
till the dis-
6
DESCRIPTION
SYSTEM REACTION
When is detected a dry-
run operation the pump is
automatically stopped. By
mean of ENTER the normal
operation can be manually
restored.
After the activation of the
dry-running alarm if the
Automatic system reset
DRY RUNNING
(ART) is enabled, a first
attempt at 5 minutes and
then an attempt every 30
minutes for 24 hours is
performed in order to res-
tore the normal operation.
This alarm can also be reset
manually with the ENTER
push-button. If the alarm
persists after 24 h we find a
definitive alarm.
It detects pressure be-
low a pre-set value and
for a pre-set period in the
ADVANCED PROGRAM-
MING MENU. The minimum
pressure helps to detect
MINIMUM
PRESSURE
a dry-run operation or
pumps running far from its
best efficiency point. This
alarm is reset automatically
as soon as the pressure
exceeds the limit value.
Overcurrent alarm is acti-
vated when the nominal
pump current is exceeded.
4 automatic reset attempts
OVERLOAD
prior to the final alarm are
performed.
Normal operation can also
be restored manually by
pressing ENTER.
DAMAGED
CONTACT WITH YOUR
PRESSURE
SUPPLIER
TRANSMITTER

Publicité

Table des Matières
loading

Table des Matières