IMEON INVERTER
3.10.1 Generator relay
The integrated relay allows automatically starting and stopping the diesel generator via a dry contact
depending on thebatterystate of charge. The power supply of the generator must be connected to the
"GRID CONNECTION" input of the inverter and cannot be used at the same time as the public
network.
WARNING: The generator must be equipped with a voltage regulator and a frequency regulator.
The output of the generator must comply with the AC input voltage specifications of the IMEON (N/PE
=0 Vac) to be checked prior to connection to IMEON.
The generator will charge the batteries connected to the IMEON through the "GRID CONNECTION"
terminal as soon as the voltage of battery bank is below the "battery cut-off voltage when grid is
available" threshold. The generator will stop automatically. The generator will stop charging the
batteries when the battery pack is recharged.
In order to use this function, you need to go toIMEON OS. ONE, page "Module", then enable the "Genstart"
module and configure the module. It will auto-configure certain settings of the inverter. To learn more about
auto-configuration, refer to the module description.