UPS
TECHNICAL DATA TABLE
MODELS
INPUT (1 Ø + N star configuration voltages)
Nominal voltage
Acceptable range
Voltage range for which no battery intervention
Nominal frequency
Maximum current (1)
Nominal current (2)
Power factor
Current distortion @ maximum load
BYPASS (on L1)
Voltage range accepted for switching
Frequency range accepted for switching
Switching time
BATTERY
Recharge time (8)
OUTPUT
Nominal voltage
Static variation (3)
Dynamic variation (4)
Waveform
Voltage distortion @ linear load
Voltage distortion @ distorting load
Frequency (5)
Current peak factor
Nominal power in VA
Nominal power in W
Short circuit current
VARIOUS
Leakage current (to ground)
AC/AC yield
Ambient temperature (6)
Relative humidity
Protections
Hold-up time
Noise level
Dimension H x L x D (mm)
Weight in Kg (estimate)
T
5000VA
220 – 230 – 240 Vac single-phase
Maximum voltage 276Vac
Minimum voltage:
from 184 to 138Vac between 100% and 50% of load in linear mode
Return to mains operation at 190Vac
30A
24A
Frequency selected ±5%
220 / 230 / 240 Vac selectable ±1.5%
50 or 60 Hz selectable
5000
4000
1.5 x In per t=0.5sec
< 90 % non-condensing
Excessive battery discharge – overcurrent – short-circuit – overvoltage –
undervoltage –thermal
< 45 dB(A) at 1 m
615mm x 282mm x 785mm
89 Kg
ECHNICAL DATA TABLE
6000VA
0 - 280 Vac
50 - 60 Hz ±5 Hz
36A
28,5A
≥ 0.95
≤ 6%
180 - 264 Vac
0.1ms
6-8 h
1.5% (7)
≤ 5% in 20 ms
Sinusoidal
≤ 3%
≤ 6%
≥ 3 : 1
6000
4800
≤ 10mA
92 %
0 – 40 °C
≥ 40msec
90 Kg
63