U
SE
FUNCTION
Alarm threshold
for maximum
load
Selects the level of
Display
brightness of the LCD
brightness
Selects the operating
mode of the acoustic
Acoustic alarm
Selects the operating
Auxiliary socket
mode of the auxiliary
(power share)
Selects the allowed
input frequency range
Input frequency
for the passage onto
tolerance
synchronization of the
Selects the allowed
Bypass voltage
voltage range for the
thresholds
passage onto bypass
Selects the allowed
Bypass voltage
thresholds for
operation in ECO
ECO
Selects the sensitivity
Sensitivity of
of intervention during
intervention for
operation in ECO
ECO
Power supply of the
Power supply of
load on bypass with
the load in stand-
by
Selects the mode of
Bypass operation
use of the bypass line
56
DESCRIPTION
PREDEFINED
Selects the user
overload limit
display
alarm
socket
ADVANCED SETTINGS
bypass and for
output
Low:
High: 264V
voltage range for
Low:
High: 253V
mode
mode
Disabled (load
UPS switched off
NOT powered)
(stand-by state)
High sensitivity
POSSIBLE CONFIGURATIONS
• Disabled
Disabled
• 0 ÷ 103 in 1% steps
Maximum
Minimum ÷ Maximum in 20 steps
• Normal
Low
• Low: does not sound for momentary
bypass intervention
• Always connected
• Disconnection after n seconds of
Always
operation from battery
• Disconnection after n seconds from
connected
the end of discharge prealarm signal
• ... (see UPSTools manual)
• ± 0.25%
• ± 0.5%
± 5%
• ± 0.75%
• ± 1÷ ±10 in 1% steps
180V
Low: 180 ÷ 200 in 1V steps
High: 250 ÷ 264 in 1V steps
200V
Low: 180 ÷ 220 in 1V steps
High: 240 ÷ 264 in 1V steps
• Low
• Normal
Normal
• High
• Disabled (not powered)
• Enabled (powered)
• Enabled/High sensitivity
• Enabled/Low sensitivity
• Disabled with input/output
Enabled /
synchronization
• Disabled without input/output
synchronization
MODE