Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

UPS
CONFIGURATION
The following table shows all the possible configurations available to adapt the UPS to the user's
requirements.
KEY:
=
=
FUNCTION
To select the nominal
Output frequency
To select the nominal
Output voltage
To select one of the 4
Operating mode
different operating
Start-up delay
automatic restart after
Automatic shutdown
Shutdown due to
operation from the
minimum load
battery if the load is
Maximum time of
Back up time
operation from the
limit
Estimated remaining
End of discharge
back up time for the
alert
end of discharge alert
Time interval for the
Battery test
automatic battery test
Indicates that the configuration can be changed from the display panel as well as by
means of the configuration software.
Indicates that the configuration can only be changed via the configuration software.
DESCRIPTION
PREDEFINED
output frequency
output voltage
ON LINE
modes
Delay before
the mains returns
of the UPS in
less than 5%
battery
POSSIBLE CONFIGURATIONS
• 50 Hz
• 60 Hz
Auto
• Auto: automatic sensing from the input
frequency
• 220V
• 230V
230V
• 240V
• 220 ÷ 240 in 1V steps
(only via software)
• ON LINE
• ECO
• SMART ACTIVE
• STAND-BY OFF
• Disabled
5 sec.
• 1 ÷ 255 in 1 sec. steps
• Enabled
Disabled
• Disabled
• Disabled (full battery discharge)
Disabled
• 1 ÷ 65000 in 1 sec. steps
3 min.
1 ÷ 255 in 1 min. steps
• Disabled
40 hours
• 1 ÷ 1000 in 1 hour steps
U
SE
MODE
55

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

6000va6500va8000va10000va

Table des Matières