Electrical

Disconnect power before working on pump, motor, pressure switch, or wiring.
MOTOR SWITCH SETTINGS
NOTE: 1/2 HP motors are wired for 115 volts only, and have no motor wiring to change.
3/4 HP or 1 HP motor terminal boards (located under the motor end cover) should look like the one below.
If the motor can operate at either 115 or 230 volts, it is set at the factory to 230 volts. Do not change motor wiring
if line voltage is 230 volts, or if you have a single voltage motor.
Never wire a 115 volt motor to a 230 volt line.
Dial Type Voltage Selector
Voltage is factory set to 230 volts. To change to 115 volts:
1. Make sure power is off.
2. Turn the dial counter-clockwise until 115 shows in
the dial window as shown in Figure 15.
3. Attach the incoming power leads to the two outer
screws on the pressure switch as shown in Figure 14.
4. Attach the ground wire to the grounding connections
as shown in Figure 14.
5. If there are other wires, they should be capped.
6. Reinstall the Motor end cover.
For parts or assistance, call Simer Customer Service at
Power Supply Connections
Voltage
Change
Dial
Ground Wire Connection
Figure 14: Voltage set to 230 volts, Dial Type
Figure 15: Voltage set to 115 volts, Dial Type
1-800-468-7867 / 1-800-546-7867
9
Pressure Switch