Connect Ventilation Ducts; Connect Unit - Helios KWL 170 W Notice De Montage Et D'utilisation

Masquer les pouces Voir aussi pour KWL 170 W:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
EN
ATTENTION
CHAPTER 5
ELECTRICAL
CONNECTION
m
DANGER
ATTENTION
Central ventilation unit – KWL 170 W/W ET
6. Connect condensate hose (length max. 1.5 m) to the building drainage system (see Fig. 22).
Condensat hose DN 12 mm
(note gradient!)
7. The ball siphon must be inspected:
– In order to guarantee the absence of leaks, the ball siphon must not be subjected to lateral loads due to the con-
densate hose during installation!
– The drainage pipe route must not rise behind the siphon! Ensure that there are no air pockets during installation!
– The condensate outlet must be frost-proof!
Water damage in the unit due to condensation.
If the "cold recovery" function is activated and the plugs in the condensate tray have not been removed, this can
result in water damage in the unit because the condensate cannot drain freely.
> If the "cold recovery" function is used, the plugs in the condensate tray must be removed.
> The function must be activated or deactivated in the unit control system according to the application.
4.4

Connect ventilation ducts

The units are equipped with four spigots (Ø 125 mm) for connection to the duct system. The ventilation ducts must be
connected firmly and tightly to the spigots. Duct connectors RVBD 12 K (accessories) must be used in this respect.
The arrangement of ventilation ducts (supply air, extract air, intake air and exhaust air) is shown in Fig. 10 and Fig. 11
on page 12.
5.1

Connect unit

m
Danger to life due to electric shock!
An electric shock can result in death or serious injuries.
> Before any maintenance and installation work or before opening the cover, the unit must be fully isolated from
the power supply.
> The electrical connection may only be carried out by an authorised electrician according to the wiring diagrams.
Unit damage due to the unnoticed resetting of the electrical pre-heater's thermal contact switch!
The unnoticed resetting of the electrical pre-heater's thermal contact switch can result in unit damage.
> When using an electric pre-heater (KWL-EVH), the unit must not be regularly activated or deactivated via an
external switching device (e.g. timer) in the unit supply line.
1. Connect unit in accordance with the connection diagrams. When using an electric pre-heater (KWL-EVH), a timer
must not be integrated into the unit supply line.
2. Install isolator and main switch.
An isolator and main switch (accessories) must be integrated in the unit supply line. The contact opening must be at
least 3 mm. The isolator and main switch must be secured against unintended restart by suitable means.
If a residual current circuit breaker is installed in the supply line of the unit, the residual current circuit breaker must
have the following technical features: Type A or B with a rated differential current of 30 mA.
The unit has a leakage current of AC 0.7 mA and DC < 0.1 mA.
Fig. 22
15