Eaton CROUSE-HINDS Série Mode D'emploi page 21

Fiche et prise de 125 a, à 4 pôles et 5 pôles, pour atmosphères explosives
Masquer les pouces Voir aussi pour CROUSE-HINDS Série:
Table des Matières

Publicité

Fig. 1
Wall mounting bracket
side
Fig. 2
7
9
2
Safety instructions
This "Annex to operating in­
structions" GHG5107004P0011
is only for use with the origi­
nal operating instructions
"GHG 510 7004 P0001" . The
GHG 515 plugs and sockets are not suit­
able for Zone 0 and Zone 20 hazardous
areas.
Observe the national safety rules and regu­
lations for prevention of accidents as well
as the safety instructions included in these
operating instructions and set in italics the
same as this text!
Explosion-protected plugs and sockets 125 A, GHG 515
1
Technical data
1.1 Plug and socket GHG 514
IECEX type examination certificate:
top/bottom
Category of application:
EN 60079-0
Rated voltage:
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3:
Perm. ambient temperature:
catalogue version, special versions permit deviating temperatures.
Perm. storage temperature in original packing: -20° C to +40° C
**Protection category acc. to IEC/EN 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to IEC/EN 61140:
Cable entry:
wall socket
Supply terminals:
terminals L, N
terminals PE
external PE connection
Test torques:
Cover screws
Terminals
External PE connection
Weight:
wall socket
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
3
Field of application
The plugs and sockets GHG 515 are suitable
for use in Zone 1, 2 and 21, 22 hazardous
areas acc. to IEC/EN 60079-10-1 and
IEC/EN 60079-10-2!
The enclosure materials employed, including
the exterior metal parts, are made of high-
quality materials which ensure a corrosion
protection and resistance to chemical sub-
stances corresponding to the requirements in
a "normal industrial atmosphere":
In case of use in an extremely aggresesive
atmosphere, please refer to manufacturer.
EATON's Crouse-Hinds Business
single-wire connection
single-/ multi-wire connection
4/5-pole
GHG 515 45
- impact resistant polyamide
- glass-fibre reinforced polyester
- special steel AISI 316 L
IECEX BVS in progress
Ex de II C T5(T6) Gb
Ex tb IIIC T 80°C Db IP66
up to 690 V, 50/60 Hz
max. 125 A
max. 125 A without thermal protection
max. 160 A gL with thermal protection
(therm. protection set to 125A)
up to 690V / 125 A
-20° C to +40° C (T6); to +45° C (T5)
IP 66 (catalogue version)
II - is complied with by the devices
(catalogue version)
2x blanking plug M50
Cross section
Stripped wire length
70 mm² - 95 mm²
30 mm
35 mm² - 135 mm²
35 mm
4.0 - 50 mm²
2,5 Nm
12 Nm
8 Nm
(catalogue version)
approx. 23.7 kg
690V VAC
20A
AC 15
400V / 6A
DC 13
24V / 2A
4
Use/Properties
The GHG 515 plugs and sockets are used for
the power supply of local controls with varying
locations, as well as of electrical installations,
mobile machinery and driving gear in hazard-
ous areas. The plugs and sockets can also be
used in a „normal industrial area" .
The low-voltage plugs and sockets GHG 515
are fitted with a load break switch and can be
used up to max. 125 A (see technical data).
The plugs and sockets can generally be used
for the voltage range laid down in
IEC/EN 60309 (e.g. U
400V that corresponds
N
to the voltage range 380-415V).
The apparatus connected to the plug shall
be suitable for the applied mains voltage.
The plug can be pushed into the socket and
pulled out of it only whilst the socket ist
switched off.