3. Compare both values.
If the value given in Tab. 2 is smaller than the total cable length given in Tab. 1, repeaters
must be used. Repeaters divide the total cable length into segments.
Note!
Note the reduction of the total cable length due to the signal delay of the
ƒ
repeater (see example
Mixed operation
ƒ
– Mixed operation is available if different nodes are operated on the same
mains.
– If the total cable lengths of the participants are different at the same
baud rate, the smaller value must be used in order to determine the
max. cable length.
Example: Selection help
Given:
Cable cross-section:
Number of nodes:
Repeater:
At maximum number of nodes (63) the following cable lengths/number of repeaters must
be complied with:
Baud rate [kbps]
Max. cable length [m]
Segment cable length [m]
Number of repeaters
Check repeater application
Given:
Baud rate:
Cable cross-section:
Number of nodes:
Cable length:
EDK82ZAFCC-210 DE/EN/FR 4.0
).
55
2
0.5 mm
(according to cable specification 49)
63
Lenze repeater, type 2176 (cable reduction: 30 m)
20
50
3900
1500
310
310
13
5
125 kbps
2
0.5 mm
28
450 m
Electrical installation
Bus cable length
125
250
590
250
310
250
1
-
6
500
80
80
-
55